William Taft High School was last inspected on February 26, 2026 with a result of “Pass w/ Conditions”. Inspectors found 3 violations, 1 of them critical.
Latest inspection
February 26, 2026 · Canvass
Result: Pass w/ Conditions
1 critical2 general-
CriticalManagement & training
No written plan or kit for cleaning up vomit or diarrhea.
Inspector’s note: Observed no kit and procedure on site for responding to vomit and diarrhea at time of inspection. Instructed to maintain kit containing all necessary supplies including a sanitizer rated as effective against norovirus on site at all times. Priority foundation violation 7-38-005. No citation issued.
Official wording (code 5)
Procedures for responding to vomiting and diarrheal events
-
GeneralFacility upkeep
Equipment or surfaces were in poor repair or made of material that can’t be cleaned.
Inspector’s note: Observed torn gasket on door of walk-in freezer. Instructed to repair or replace and maintain in good condition.
Official wording (code 47)
Food & non-food contact surfaces cleanable, properly designed, constructed & used
-
GeneralFacility upkeep
Ventilation or lighting was inadequate.
Inspector’s note: Observed minor build up of dust on fan in first walk in cooler. Instrcuted to clean and maintain
Official wording (code 56)
Adequate ventilation & lighting; designated areas used
Inspection history
27 inspections on record
-
Pass
Canvass · Pass
1 critical3 general Show violations
-
CriticalFood handling
Surfaces that touch food weren’t cleaned and sanitized.
Inspector’s note: Observed slight build up of residue in interior of ice machine used to produce ice for human consumption.
Official wording (code 16)
Food-contact surfaces: cleaned & sanitized
-
GeneralFacility upkeep
Equipment or surfaces were in poor repair or made of material that can’t be cleaned.
Inspector’s note: Observed torn gasket on door of middle walk-in cooler. Instructed to repair or replace and maintain in good condition.
Official wording (code 47)
Food & non-food contact surfaces cleanable, properly designed, constructed & used
-
GeneralFacility upkeep
Plumbing problems, or missing protection against backflow.
Inspector’s note: Observed low water pressure at exposed handwashing sink located opposite 3 compartment sink. Instructed to repair or replace and maintain in good condition.
Official wording (code 51)
Plumbing installed; proper backflow devices
-
GeneralFacility upkeep
Ventilation or lighting was inadequate.
Inspector’s note: Observed 1 burnt out lightbulb in ceiling of staff men's toilet room located off kitchen. Instructed to correct and maintain in good condition.
Official wording (code 56)
Adequate ventilation & lighting; designated areas used
-
-
Pass
Canvass Re-Inspection · Pass
No violations
-
Fail
Canvass · Fail
3 critical Show violations
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: OBSERVED NO SOAP AT THE HAND WASHING SINK IN THE CANTEEN. INSTRUCTED TO CORRECT AND MAINTAIN SOAP AT ALL TIMES. PRIORITY FOUNDATION VIOLATION 7-38-030(c). NO CITATION ISSUED.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: OBSERVED NO PAPER TOWELS AT THE HAND WASHING SINK IN THE CANTEEN. INSTRUCTEDD TO CORRECT AND MAINTAIN AT ALL TIMES. PRIORITY FOUNDATION VIOLATION N7-38-030(c). NO CITATION ISSUED.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: OBSERVED HAND WASHING SINK IN CANTEEN AREA DOES NOT TURN ON. INSTRUCTED TO CORRECT AND MAINTAIN HOT AND COLD RUNNING WATER UNDER PRESSURE AT ALL TIMES. PRIORITY FOUNDATION VIOLATION 7-38-030(c). NO CITATION ISSUED.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
-
Pass
Canvass Re-Inspection · Pass
No violations
-
Fail
Canvass · Fail
2 critical Show violations
-
CriticalManagement & training
No written plan or kit for cleaning up vomit or diarrhea.
Inspector’s note: Found no vomit and diarrheal clean up procedure with spill kit(sanitizer spray for norovirus).priority violation.no citation issued.7-38-005.must provide.
Official wording (code 5)
Procedures for responding to vomiting and diarrheal events
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: Found no hot running water at hand sinks at serving line and kitchen by 3 compartment sink.priority violation.no citation issued.7-38-030c.must reapir.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
-
Conditional
Canvass · Pass w/ Conditions
1 critical Show violations
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: Observed no handwashing sink on serving line where open food is dispensed and served. Install handwashing sink with hot and cold running water soap and paper towels. Priority foundation violation 7-38-030 no citation issued
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
-
Pass
Canvass · Pass
1 critical3 general Show violations
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: Instructed to provide handwashing signage at all handsink in prep/dishwashing area.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
GeneralFacility upkeep
Equipment and surfaces were dirty.
Inspector’s note: Instructed to clean and maintain interior surfaces of ice machine with minimal calcium build-up.
Official wording (code 49)
Non-food/food contact surfaces clean
-
GeneralFacility upkeep
Equipment and surfaces were dirty.
Inspector’s note: Instructed to clean and maintain counter shelves behind service area
Official wording (code 49)
Non-food/food contact surfaces clean
-
GeneralFacility upkeep
Garbage wasn’t handled or stored properly.
Inspector’s note: Instructed to clean and maintain rear outside garbage area. Must remove unnecessary articles/clutter to prevent pest harborage.
Official wording (code 54)
Garbage & refuse properly disposed; facilities maintained
-
-
Conditional
Canvass · Pass w/ Conditions
1 critical4 general Show violations
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: OBSERVED NO EXPOSED HAND SINK ACCESSIBLE AT THE THREE COMPARTMENT SINK .INSTRUCTED MANAGEMENT TO INSTALL AN EXPOSED HAND SINK NEXT TO THE THREE COMPARTMENT SINK. PRIORITY FOUNDATION VIOLATION 7-38-030 (c) NO CITATION ISSUED
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
GeneralFacility upkeep
Plumbing problems, or missing protection against backflow.
Inspector’s note: Observed washbowl sinks in restrooms at academic center with loose faucet and handles.instructed management to repair sinks mentioned
Official wording (code 51)
Plumbing installed; proper backflow devices
-
GeneralFacility upkeep
Sewage or wastewater wasn’t disposed of properly.
Inspector’s note: Observed no grease trap under three compartment sink.instructed management to install or locate the grease trap at the three compartment sink.
Official wording (code 52)
Sewage & waste water properly disposed
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Observed dirty walls in mop sink closets.instructed management to clean and maintain mop sink closets.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Ventilation or lighting was inadequate.
Inspector’s note: Observed burn't out lights and cracked light shield over dishwashing area.instructed management to replace light bulbs and broken shields.
Official wording (code 56)
Adequate ventilation & lighting; designated areas used
-
-
Conditional
Canvass Re-Inspection · Pass w/ Conditions
1 critical2 general Show violations
-
CriticalManagement & training
No written plan or kit for cleaning up vomit or diarrhea.
Inspector’s note: Observed no clean-up of vomiting and diarrhea procedure and clean-up kit not complete on premises during inspection (missing mask and chemicals for sanitation). Instructed to have said procedure along with required equipment for clean-up. Priority foundation violation. No citation issued. 7-38-005
Official wording (code 5)
Procedures for responding to vomiting and diarrheal events
-
GeneralFacility upkeep
Plumbing problems, or missing protection against backflow.
Inspector’s note: Back flow prevention devices not located at ice machine machine. Must install back flow prevention devices or air gap between the water supply inlet and the unit so it may be located to be serviced and maintained.
Official wording (code 51)
Plumbing installed; proper backflow devices
-
GeneralFacility upkeep
Toilet rooms weren’t built, stocked, or cleaned properly.
Inspector’s note: Must provide toilet room receptacle with cover for sanitary napkins in lady's bathroom
Official wording (code 53)
Toilet facilities: properly constructed, supplied, & cleaned
-
-
Fail
Canvass · Fail
2 critical3 general Show violations
-
CriticalManagement & training
No written plan or kit for cleaning up vomit or diarrhea.
Inspector’s note: Observed no clean-up of vomiting and diarrhea procedure and clean-up kit not complete on premises during inspection (missing mask and chemicals for sanitation). Instructed to have said procedure along with required equipment for clean-up. Priority foundation violation. No citation issued. 7-38-005
Official wording (code 5)
Procedures for responding to vomiting and diarrheal events
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: OBSERVED THAT SEVERAL HAND WASHING SINKS ON SECOND FLOOR ACADEMIC CENTERS DO NOT HAVE PROPER REQUIRED TEMPERATURE OF WATER (100 F). MEASURED WATER TEMPERATURE OBSERVED TO BE BELOW 90 F.PRIORITY VIOLATION. 7-38-030(c) NO CITATION ISSUED MANAGEMENT ADVISED TO USE FACILITY WITH WORKING HAND WASHING SINKS
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
GeneralFacility upkeep
Plumbing problems, or missing protection against backflow.
Inspector’s note: Back flow prevention devices not located at ice machine machine. Must install back flow prevention devices or air gap between the water supply inlet and the unit so it may be located to be serviced and maintained.
Official wording (code 51)
Plumbing installed; proper backflow devices
-
GeneralFacility upkeep
Toilet rooms weren’t built, stocked, or cleaned properly.
Inspector’s note: Must provide toilet room receptacle with cover for sanitary napkins in lady's bathroom
Official wording (code 53)
Toilet facilities: properly constructed, supplied, & cleaned
-
GeneralFacility upkeep
Garbage wasn’t handled or stored properly.
Inspector’s note: OBSERVED THAT BOTH TRASH OUTSIDE RECEPTACLES HAVE BROKEN LIDS AND ARE NOT COVERED.PRIORITY FOUNDATION VIOLATION. 7-38-020(b) NO CITATION ISSUE
Official wording (code 54)
Garbage & refuse properly disposed; facilities maintained
-
-
Pass
Canvass · Pass
4 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: Instructed to defrost and maintain the 3-door reach-in freezer to remove frost buildup on the condenser and ceiling.
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: Must replace the missing handle for the top drawer where utensils are stored on the line and maintain.
-
GeneralMinor (pre-2018 form)
Food and non-food contact equipment utensils clean, free of abrasive detergents
Inspector’s note: Instructed to detail clean the bottom shelf of the 3-door reach-in refrigerator in the prep area and maintain.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Must increase the hot and cold running water sensor times to a minimum of 15 seconds in the men's and women's faculty and student washrooms on the 2nd floor.
-
-
Pass
Canvass · Pass
5 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: Observed the hot box in the sending school area to have a damaged handle on the top door. Instructed facility to repair and maintain.
-
GeneralMinor (pre-2018 form)
Food and non-food contact equipment utensils clean, free of abrasive detergents
Inspector’s note: Observed the left side teacher's fridge in the faculty lounge to have heavy dirt and food accumulation inside. Instructed facility to clean and maintain. Observed slight calcium buildup in the upper interior portion of the ice machine. Instructed facility to clean, sanitize, and maintain.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Observed dirt and debris on floors left from overnight cleaning in various areas: throughout main hallways, in the faculty/staff rear hallways, and in the elevator. Instructed facility to clean and maintain.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Observed the 3-1 janitor's closet wall to have loose peeling paint. Instructed facility to remove, repaint, and maintain.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Observed a small leak at the right faucet base at the three compartment sink. Instructed facility to repair and maintain. Observed the 2nd floor men's faculty washroom to have one timed faucet sink not working and one not staying on for required 15 seconds. Instructed facility to repair and maintain. Observed a urinal in the first floor boys washroom near the main entrance to not flush. Instructed facility to repair and maintain.
-
-
Pass
Canvass · Pass
5 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact equipment utensils clean, free of abrasive detergents
Inspector’s note: Instructed to detail clean and maintain storage racks with dried milk spillage inside dairy walk-in cooler and interior of ice machine in rear area.---------must detail clean and maintain interior surfaces of (3) microwave ovens with excessive dried food debris in 2nd floor teachers lounge to prevent pest harborage .
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Instructed to detail clean and maintain floors throughout dining area with excessive food and dirt debris, hallway floors throughout (1st, 2nd, 3rd floor) building.---------must detail clean and maintain floors inside all janitor's closet (room 1-1, 1-2, 1-3, 1-4, 2-1, 2-2, 2-3, 2-4, 3-1, 3-2, 3-3, 2-4) with heavy dust, garbage and dirt accumulation and floors inside electrical closet in rear (by dining area).
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Noted post wall in middle of dining room in poor repair with opening. Instructed to seal/fix.--------must repair mop sink wall inside janitor's closet room 3-1.--------must detail clean and maintain walls with dried food and milk spillage around dining area.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Instructed to repair faucet neck/handle at wash compartment of the 3 compartment sink.------noted prep sink in poor repair, slow draining in sending school area or the pizza area. Instructed to fix and maintain.
-
GeneralMinor (pre-2018 form)
Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored
Inspector’s note: Instructed to detail clean, maintain and remove clutter stored inside all janitor's closet.-------must remove unused equipment in rear storage area.
-
-
Pass
Complaint Re-Inspection · Pass
1 general Show violations
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Floor in corners of kitchen, behind equipment in teacher's lounge, utility closet and compressor rooms not clean. Instructed to detail clean daily.
-
-
Fail
Short Form Complaint · Fail
3 general Show violations
-
GeneralSerious (pre-2018 form)
No evidence of rodent or insect outer openings protected/rodent proofed, a written log shall be maintained available to the inspectors
Inspector’s note: Observed numerous mice dropping in adjacent rooms of cafeteria-utility closet behind door-approximately 30 mice droppings, in teacher's lounge behind both refrigators-approximately 80 on bottom ledge of refrigator and on floor, inside compressor room in corner behind door approximately 30, in corner behind copier machine in teacher's lounge approximately 30. Instructed to have licensed pest control service premises and provide service invoice for services provided. Remove all droppings, detail clean and sanitize areas. Serious violation 7-38-020 no citation issued.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Floor in corners of kitchen, behind equipment in teacher's lounge, utility closet and compressor rooms not clean. Instructed to detail clean daily.
-
GeneralMinor (pre-2018 form)
Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored
Inspector’s note: Teacher's lounge behind equipment cluttered and not clean. Instructed to remove all unused articles and kee area maintained.
-
-
Fail
Complaint-Fire Re-inspection · Fail
1 critical4 general Show violations
-
CriticalCritical (pre-2018 form)
No evidence of rodent or insect infestation, no birds, turtles or other animals
Inspector’s note: On invoice #376349 was provided for sweeps for doors
-
GeneralSerious (pre-2018 form)
Outside garbage waste grease and storage area; clean, rodent proof, all containers covered
Inspector’s note: violation corrected lids closed.
-
GeneralSerious (pre-2018 form)
Outside garbage waste grease and storage area; clean, rodent proof, all containers covered
Inspector’s note: Garbage dumpster leaking,we observed excess food liquids,grimes and black slime substance build-up at base of the dumpster and all around the garbage dumpster and cement ground. Instructed to clean and maintain ground repair/reseal said dumpster. Serious violation:7-38-020 no citation issued
-
GeneralSerious (pre-2018 form)
Dish washing facilities: properly designed, constructed, maintained, installed, located and operated
Inspector’s note: Three compartment sink not properly maintained. The east end of the sink there is a motor that moves the water around but is no longer in use leaving areas inaccessible for cleaning,observed excess grime and debris inside the opened motor.. Instructed to repair or replace sink so that all surfaces are smooth and easily cleanable. Must use food grade material and non-rust material . Serious violation:7-38-030 no citation issued
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Floors throughout the prep/kitchen area not maintained:uneven /porous under hot holding unit,broken cement and paint peeling unable to clean.must repair said floor throughput the said area,surface must be smooth,cleanable and non-absorbent material. Floor throughout the dining area not maintained,we observed grimes left behind from floor machine,debris under the tables and around the feet of pole of the chairs.instructed to proper clean said area and maintain.
-
-
Fail
Complaint-Fire Re-inspection · Fail
6 general Show violations
-
GeneralSerious (pre-2018 form)
Food protected during storage, preparation, display, service and transportation
Inspector’s note: Interior of ice machine not maintained.black substance was observed where ice is made and back and side panels if the ice bin.instructed to clean,sanitize and maintain said unit.ice is for human consumption. Serious violation:7-38-005(a)
-
GeneralSerious (pre-2018 form)
Outside garbage waste grease and storage area; clean, rodent proof, all containers covered
Inspector’s note: Outside garbage dumpsters not maintained. All three dumpster overfilled with garbage and lids not able to close. On ground and around containers food debris,empty milk containers and dirty cardboard around.instructed to clean area mentioned and keep lids closed at all times to minimize rodent/ insects activities. Serious violation: 7-38-020 no citation issued
-
GeneralSerious (pre-2018 form)
Dish washing facilities: properly designed, constructed, maintained, installed, located and operated
Inspector’s note: Three compartment sink not properly maintained. The east end of the sink there is a motor that moves the water around but is not longer in use leaving areas inaccessible for cleaning,observed excess grime and debris inside the opened motor.. Instructed to repair or replace sink so that all surfaces are smooth and easily cleanable. Must use food grade material and non-rust material . Serious violation:7-38-030 no citation issued
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Floors throughout the prep/kitchen area not maintained:uneven /porous under hot holding unit,broken cement and paint peeling unable to clean.must repair said floor throughput the said area,surface must be smooth,cleanable and non-absorbent material. Floor throughout the dining area not maintained,we observed grimes left behind from floor machine,debris under the tables and around the feet of pole of the chairs.instructed to proper clean said area and maintain.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Stained and dusty ceiling tiles at unused dish room, need to replace.(however room is used for other activities)
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Leaking pipe under the three compartment sink,instructed to seal with a smooth and cleanable material.
-
-
Fail
Complaint · Fail
4 critical7 general Show violations
-
CriticalCritical (pre-2018 form)
Sanitizing rinse for equipment and utensils: clean, proper temperature, concentration, exposure time
Inspector’s note: OBSERVED EMPLOYEE WASHING RINSING AND STORING POT WITHOUT SANITIZING MULTI USE UTENSILS.MANAGER SET UP THREE COMPARTMENT SINK: WASH,RINSE AND SANITIZE 200ppm CRITICAL VIOLATION:7-38-030 NO CITATION ISSUED
-
CriticalCritical (pre-2018 form)
Adequate number, convenient, accessible, designed, and maintained
Inspector’s note: No hot water provided at washbowl at men's washroom,inside the kitchen,wash room is used by the kitchen staff. Second floor teacher's lounge no hot water provided at washbowl. No hot water provided at washbowls at boys washroom second floor. Girls washroom no hot water provided at second floor. Must provided hot water at mentioned sinks.other wash room available to students and employees with hot / cold running water. Critical violation:7-38-030 no citation issued.
-
CriticalCritical (pre-2018 form)
Hand washing facilities: with soap and sanitary hand drying devices, convenient and accessible to food prep area
Inspector’s note: Hand drying device broken at girls washroom at second floor,no paper towels provided.instructed to provide hand drying device or paper towels at said washroom.premises has other washroom with soap and working hand drying device. Upon my request paper towels was provide at said wash bowls. Critical violation:7-38-030 citation issued.
-
CriticalCritical (pre-2018 form)
No evidence of rodent or insect infestation, no birds, turtles or other animals
Inspector’s note: Visual evidence mice droppings,in multiple locations of kitchen: droppings were observed at unused dish room.approx 20 mice droppings under the exposed hand sink(south-west corner);along baseboard north and east baseboard wall approx 50 droppings.approx 75 mice droppings were observed under and behind cooking equipment on both side of the prep area;approx 30 droppings under the one compartment sink across from walk-in cooler.approx 30 mice dropping were observed under the three compartment south-east corner.approx 10 mice dropping under table at south wall of the kitchen by the walk-in freezer.three mice droppings were observed at ledge of steam table serving line. Approx 20 mice droppings at front(east serving area)serving line.outer openings not protected found front and side doors are not rodent/insect proof.all doors should have tight fitting at bottoms and between doors. Instructed
-
GeneralSerious (pre-2018 form)
Food protected during storage, preparation, display, service and transportation
Inspector’s note: Interior of ice machine not maintained.black substance was observed where ice is made and back and side panels if the ice bin.instructed to clean,sanitize and maintain said unit.ice is for human consumption. Serious violation:7-38-005(a)
-
GeneralSerious (pre-2018 form)
Outside garbage waste grease and storage area; clean, rodent proof, all containers covered
Inspector’s note: Outside garbage dumpsters not maintained. All three dumpster overfilled with garbage and lids not able to close. On ground and around containers food debris,empty milk containers and dirty cardboard around.instructed to clean area mentioned and keep lids closed at all times to minimize rodent/ insects activities. Serious violation: 7-38-020 no citation issued.
-
GeneralSerious (pre-2018 form)
Dish washing facilities: properly designed, constructed, maintained, installed, located and operated
Inspector’s note: Three compartment sink not properly maintained. The east end of the sink there is a motor that moves the water around but is not longer in use leaving areas inaccessible for cleaning,observed excess grime and debris inside the opened motor.. Instructed to repair or replace sink so that all surfaces are smooth and easily cleanable. Must use food grade material and non-rust material . Serious violation:7-38-030 no citation issued
-
GeneralMinor (pre-2018 form)
Food and non-food contact equipment utensils clean, free of abrasive detergents
Inspector’s note: Hood and filters with a build-up of dust that dangling from filters,instructed to clean and maintain
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Floors throughout the prep/kitchen area not maintained:uneven /porous under hot holding unit,broken cement and paint peeling unable to clean.must repair said floor throughput the said area,surface must be smooth,cleanable and non-absorbent material. Floor throughout the dining area not maintained,we observed grimes left behind from floor machine,debris under the tables and around the feet of pole of the chairs.instructed to proper clean said area and maintain.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Stained and dusty ceiling tiles at unused dish room, need to replace.(however room is used for other activities)
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Leaking pipe under the three compartment sink,instructed to seal with a smooth and cleanable material.
-
-
Conditional
Canvass · Pass w/ Conditions
1 critical4 general Show violations
-
CriticalCritical (pre-2018 form)
Hand washing facilities: with soap and sanitary hand drying devices, convenient and accessible to food prep area
Inspector’s note: Observed girls washroom hand drying device not working/no hand towels (by cafeteria), no soap in mens faculty washrooms (3rd floor and 1st floor southwest corner). Instructed manager to provide soap and paper towels/working hand drying device in all washrooms for good hygienic practices. Critical violation 7-38-030. No citation issued.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Observed dirt/dust build up on floor in mop sink closets. Instructed manager to clean floor at all mop sink rooms.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: No backflow prevention device at ice machine also mop sink hot/cold water handles stripped at 2nd floor mop closet room (south east corner). Instructed manager to provide and make visible backflow prevention device for ice machine and repair/replace said water handles.
-
GeneralMinor (pre-2018 form)
Refrigeration and metal stem thermometers provided and conspicuous
Inspector’s note: Observed missing/broken therometers in some prep coolers. Instructed manager to provide/make visible thermometers for all coolers.
-
GeneralMinor (pre-2018 form)
Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored
Inspector’s note: 2nd floor womens washroom floor cluttered (northwest corner). Instructed manager to remove all items.
-
-
Pass
Complaint Re-Inspection · Pass
1 general Show violations
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Clean fans and vents inside bathrooms through out premises(heavy dust particles).
-
-
Fail
Complaint · Fail
2 critical3 general Show violations
-
CriticalCritical (pre-2018 form)
Facilities to maintain proper temperature
Inspector’s note: Noted temperature of walk in cooler (middle) at the food prep area to be improper at 52.6f. Manager immediately called company for repairs. Instructed not to use cooler until proper temperature of 40f or below is attained. Premises has other coolers maintaining temperatures of 40f and below. Citation issued for critical violation #7-38-005(a)
-
CriticalCritical (pre-2018 form)
Potentially hazardous food meets temperature requirement during storage, preparation display and service
Inspector’s note: Noted internal temperatures of the following potentially hazardous food items inside walk in cooler to be improper between 44f to 60f. Yogurt 60.2f, lunch meat 46.3f, turkey 45.8f, apple juice(keep frozen)45.5f,ham 47.6f, cheese (montery jack)51.8f,cream cheese 53.6f, cheese (shredded parmesan)44.6f, vegetable base(keep refrigerated)47.7, orange juice 45.2f. Manager immediately and voluntarily disposed of products 650lbs worth $758.00 through denaturing process. Instructed to monitor equipment and receiving temperatures during delivery. Citation issued for critical violation #7-38-005(a)
-
GeneralSerious (pre-2018 form)
Outside garbage waste grease and storage area; clean, rodent proof, all containers covered
Inspector’s note: Noted outside garbage dumpster (compactor) in poor repairs leaking liquid food waste on to the ground. Engineer immediately called company to schedule maintenance. Must replace or repair and clean surrounding area. Citation issued for serious violation #7-38-020
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Instructed to clean and sanitize floors inside janitors closets/mop sink especially at the kitchen closet.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Clean fans and vents inside bathrooms through out premises(heavy dust particles).
-
-
Pass
Canvass Re-Inspection · Pass
2 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: Noted broken gasket at the bottom door of reach in cooler at the food prep area. Instructed to repair.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Instructed to repair or replace missing and stained tiles on ceilings through out premises
-
-
Fail
Canvass · Fail
7 general Show violations
-
GeneralSerious (pre-2018 form)
No evidence of rodent or insect outer openings protected/rodent proofed, a written log shall be maintained available to the inspectors
Inspector’s note: Noted over 50 mice droppings under the 1 compartment sinks at the food prep area and electrical compartment at the front serving line of the main lunch line. Instructed to clean and sanitize affected area. Citation issued for serious violation #7-38-020
-
GeneralSerious (pre-2018 form)
Adequate number, convenient, accessible, properly designed and installed
Inspector’s note: Noted no hot running water at the teachers lounge/lunch room. Temperature of water at the time of inspection was 66.4f. Also noted no hot or cold running water in one of three hand wash sinks at the womens wash room by the gym. Instructed to repair and have hot running water on all hand wash sinks for proper hand washing. Citation issued for serious violation #7-38-030
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: Noted broken gasket at the bottom door of reach in cooler at the food prep area. Instructed to repair.
-
GeneralMinor (pre-2018 form)
Food and non-food contact equipment utensils clean, free of abrasive detergents
Inspector’s note: Instructed to detail clean and sanitize the upper compartment of the ice machine.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Instructed to detail clean all floor drains at the serving line and maintain. Instructed to detail clean and sanitize floors in the boys bathroom(second floor) with cigarette stubs, cigarette ashes and toilet tissues.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Instructed to repair or replace missing and stained tiles on ceilings through out premises
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Noted slow drain at the employee hand wash sink; also noted leakage at the u-joint of exposed hand wash sink at the womens bathroom by the gym. Instructed to repair.
-
-
Pass
Canvass · Pass
4 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: Walk in cooler shelving that had peeling paint/rust, shall be repaired/replaced.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Walls that had exposed cinder blocks, walls in kitchen prep area shall be repaired/sealed, damaged, stained ceiling tiles in lunchroom, classrooms 1st floor, 2nd fl,3rd floor shall be repaired/sealed.Missing ceiling tiles in classrooms shall be provided. Peeling paint in staircases shall be repaired.
-
GeneralMinor (pre-2018 form)
Lighting: required minimum foot-candles of light provided, fixtures shielded
Inspector’s note: Missing light shields in bathrooms 3rd floor, 2nd floor shall be provided, broken/damaged and missing light shields in classrooms, bathrooms in older building shall be replaced.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Exhaust vents(ventilation) in walk in coolers, coolers not clean need cleaning(detailed), exhaust vents(ventilation) in lunchroom, classrooms 1st floor, 2nd fl, 3rd floor not clean, need cleaning(detailed).
-
-
Pass
Canvass · Pass
4 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact equipment utensils clean, free of abrasive detergents
Inspector’s note: Can opener, exhaust hood, warmer and ice machine not cleaned. Instructed to detail clean and sanitize.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Floor not maintained in canteen room and near ice machine. Instructed to repair cracked floor and reseal.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Light covers in prep area not cleaned. Instructed to detail clean. Electrical outlet near women's locker room exposed. Instructed to cover outlet. Wall below exhaust not cleaned. Instructed to detail clean and/or repaint.
-
GeneralMinor (pre-2018 form)
Food (ice) dispensing utensils, wash cloths properly stored
Inspector’s note: Ice scoop not properly stored. Instructed to store in a sanitize holder or container.
-
-
Pass
Canvass · Pass
3 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: All food and non-food contact equipment and utensils shall be smooth, easily cleanable, and durable, and shall be in good repair. RUBBER GASKET ALONG THE DOOR OF THE ICE MACHINE NOT IN GOOD REPAIR, RIPPED OFF. INSTRUCTED TO REPAIR AND MAINTAIN. BROKEN HAND DRYER OF THE MENS WASHROOM#343 NOT WORKING. INSTRUCTED TO REPAIR AND MAINTAIN. FAUCET HANDLE-HOT/COLD, WOMENS WASHROOM#331, NOT IN GOOD REPAIR. INSTRUCTED TO REPAIR AND MAINTAIN.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Cracked light shield in the dry storage room, must replace. Womens washroom #246 ceiling vent with minimal dust accumulated. Must clean in detail and maintain.
-
GeneralMinor (pre-2018 form)
Lighting: required minimum foot-candles of light provided, fixtures shielded
Inspector’s note: Rear light bulb inside the cooler and walk in freezer, by the hot holding unit, and by the fresh fruits shelve students serving area,, burned out. Instructed to replace.
-
More in ZIP 60631
Source: Chicago Department of Public Health (CDPH) open data, refreshed hourly. Last inspection 8 months ago. Always confirm with the official record.