Daniel J Corkery School was last inspected on September 24, 2026 with a result of “Pass”. Inspectors found 3 violations, 1 of them critical.

Latest inspection

September 24, 2026 · Canvass Re-Inspection

Pass

Result: Pass

1 critical2 general
  • CriticalHygiene & sanitation

    Hand sinks were missing, blocked, or not stocked with soap and towels.

    Inspector’s note: 5-202.12 (b-d) observed timed faucets not functioning properly in unisex washrooms. Water must run continuously for at least 15 seconds before reactivating faucet.

    Official wording (code 10)

    Adequate handwashing sinks properly supplied and accessible

  • GeneralFacility upkeep

    Plumbing problems, or missing protection against backflow.

    Inspector’s note: 5-205.15 observed loose middle hot water faucet on sinks in first and second floor boys' washrooms. Instructed manager to repair and maintain.

    Official wording (code 51)

    Plumbing installed; proper backflow devices

  • GeneralFacility upkeep

    Toilet rooms weren’t built, stocked, or cleaned properly.

    Inspector’s note: 5-501.17 observed no covered receptacle in first, second, and third floor unisex washrooms. Instructed manager to provide covered receptacle in all women, girls' and unisex washrooms.

    Official wording (code 53)

    Toilet facilities: properly constructed, supplied, & cleaned

Inspection history

25 inspections on record

  1. Fail

    Canvass · Fail

    2 critical4 general Show violations
    • CriticalHygiene & sanitation

      Hands weren’t washed properly or when required.

      Inspector’s note: Observed food handler washing hands in 3-compartment sink with no soap. Employees shall wash hands with soap for at least 20 seconds in an approved handwashing sink. Priority 7-38-010

      Official wording (code 8)

      Hands clean & properly washed

    • CriticalHygiene & sanitation

      Hand sinks were missing, blocked, or not stocked with soap and towels.

      Inspector’s note: Observed timed faucets not functioning properly in unisex washrooms. Water must run continuously for at least 15 seconds before reactivating faucet.

      Official wording (code 10)

      Adequate handwashing sinks properly supplied and accessible

    • GeneralPests

      Insects, rodents, or animals were present, or the building wasn’t sealed against them.

      Inspector’s note: Observed over 30 mice droppings scattered on floor, shelves, inside boxes in kitchen rear storage area, on floor inside washroom and windowsill in pre-k 001. Instructed manager to call an exterminator for service, clean and sanitize all areas. Priority foundation 7-38-020(a)

      Official wording (code 38)

      Insects, rodents, & animals not present

    • GeneralPests

      Insects, rodents, or animals were present, or the building wasn’t sealed against them.

      Inspector’s note: Observed 1/4" gap at bottom left corner of rear kitchen exit door. Instructed manager to seal all outer openings on door to prevent pest entry.

      Official wording (code 38)

      Insects, rodents, & animals not present

    • GeneralFacility upkeep

      Plumbing problems, or missing protection against backflow.

      Inspector’s note: Observed loose middle hot water faucet on sinks in first and second floo boys' washrooms. Instructed manager to repair and maintain.

      Official wording (code 51)

      Plumbing installed; proper backflow devices

    • GeneralFacility upkeep

      Toilet rooms weren’t built, stocked, or cleaned properly.

      Inspector’s note: Observed no covered receptacle in first, second, and third floor unisex washrooms. Instructed manager to provide covered receptacle in all women, girls' and unisex washrooms.

      Official wording (code 53)

      Toilet facilities: properly constructed, supplied, & cleaned

  2. Pass

    Canvass · Pass

    1 critical Show violations
    • CriticalHygiene & sanitation

      Hand sinks were missing, blocked, or not stocked with soap and towels.

      Inspector’s note: Observed missing handwashing signs in main floor and second floor restrooms. Instructed person in charge to provide and maintain handwashing signs at all handsinks.

      Official wording (code 10)

      Adequate handwashing sinks properly supplied and accessible

  3. Pass

    Canvass Re-Inspection · Pass

    1 general Show violations
    • GeneralFacility upkeep

      Plumbing problems, or missing protection against backflow.

      Inspector’s note: 5-205.15 observed 1 of 3 washbowls located in all gender restroom across from room 309 with leaky piping and pooling into bucket.

      Official wording (code 51)

      Plumbing installed; proper backflow devices

  4. Fail

    Canvass · Fail

    2 general Show violations
    • GeneralPests

      Insects, rodents, or animals were present, or the building wasn’t sealed against them.

      Inspector’s note: Observed approximately 35 small rodent droppings in the rear prep area underneath shelving units on the floor alongside the walk-in cooler, in the back room where toxic supplies are stored, behind the 2-door cooling unit alongside windows, and under 3-compartment sink basins. Instructed to remove droppings and clean and sanitize said areas. Priority foundation violation. #7-38-020 (a).no citation issued.

      Official wording (code 38)

      Insects, rodents, & animals not present

    • GeneralFacility upkeep

      Plumbing problems, or missing protection against backflow.

      Inspector’s note: Observed 1 of 3 washbowls located in all gender restroom across from room 309 with leaky piping and pooling into bucket.

      Official wording (code 51)

      Plumbing installed; proper backflow devices

  5. Pass

    Canvass Re-Inspection · Pass

    No violations

  6. Fail

    Canvass · Fail

    1 critical1 general Show violations
    • CriticalHygiene & sanitation

      Hand sinks were missing, blocked, or not stocked with soap and towels.

      Inspector’s note: OBSERVED THE HANDWASHING SINK IN THE DISH AREA RENDERED INACCESSIBLE DUE TO BOTH HOT AND COLD KNOTS MISSING MAKING THE HANDSINK INOPERABLE. INSTRUCTED TO REPAIR OR REPLACE AND MAINTAIN. PRIORITY FOUNDATION VIOLATION 7-38-030(c). NO CITATION

      Official wording (code 10)

      Adequate handwashing sinks properly supplied and accessible

    • GeneralRepeat violation

      A previously cited basic violation still wasn’t fixed.

      Inspector’s note: Observed previous core violation from report #2564134 dated: 9/22/22 not corrected: #53 no covered waste receptacle provided in the unisex employees washrooms. Must provide and maintain.

      Official wording (code 60)

      Previous core violation corrected

  7. Fail

    Canvass · Fail

    1 critical1 general Show violations
    • CriticalHygiene & sanitation

      Hand sinks were missing, blocked, or not stocked with soap and towels.

      Inspector’s note: Observed no additional exposed hand washing sink at the front serving line that is convenient to use. Management instructed to install an additional exposed hand washing sink on the opposite end of the front serving line that is supplied with hot and cold running water and soap and paper towels. Priority foundation 7-38-030(c).

      Official wording (code 10)

      Adequate handwashing sinks properly supplied and accessible

    • GeneralRepeat violation

      A previously cited basic violation still wasn’t fixed.

      Inspector’s note: Observed previous core violation from report #2531671 dated: 9/21/21 not corrected: #53 no covered waste receptacle provided in the unisex employees washrooms. Must provide and maintain.

      Official wording (code 60)

      Previous core violation corrected

  8. Conditional

    Canvass · Pass w/ Conditions

    1 critical3 general Show violations
    • CriticalHygiene & sanitation

      Hand sinks were missing, blocked, or not stocked with soap and towels.

      Inspector’s note: Observed no additional exposed hand washing sink at the front serving line that is convenient to use. Management instructed to install an additional exposed hand washing sink on the opposite end of the front serving line that is supplied with hot and cold running water and soap and paper towels. Priority foundation 7-38-030(c).

      Official wording (code 10)

      Adequate handwashing sinks properly supplied and accessible

    • GeneralFacility upkeep

      Plumbing problems, or missing protection against backflow.

      Inspector’s note: Observed broken handle in the employee toilet room located in rear kitchen area. Facility has three toilet rooms accessibles for employees to use. Must not use employee toilet room until service.

      Official wording (code 51)

      Plumbing installed; proper backflow devices

    • GeneralFacility upkeep

      Toilet rooms weren’t built, stocked, or cleaned properly.

      Inspector’s note: No covered waste receptacle provided in the unisex employees washrooms. Must provide and maintain.

      Official wording (code 53)

      Toilet facilities: properly constructed, supplied, & cleaned

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Observed dirt and debris on floor undernetah food storage shelving in kitchen food prep area. Must clean and maintain.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

  9. Pass

    Canvass · Pass

    3 general Show violations
    • GeneralFacility upkeep

      Plumbing problems, or missing protection against backflow.

      Inspector’s note: Observed handsink in front prep area slow draining as well as left side of 3 compartment sink faucet neck wobbly an loose. Instructed to repair and maintain in good condition.

      Official wording (code 51)

      Plumbing installed; proper backflow devices

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Instructed to remove all milk crates stacked up near mop sink in rear to prevent pest harborage. Must maintain premise free of clutter and unnecsary items.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Observed missing ceiling tile outside employee toiletroom. Instructed to replace and maintain.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

  10. Pass

    Canvass Re-Inspection · Pass

    2 general Show violations
    • GeneralFacility upkeep

      Equipment and surfaces were dirty.

      Inspector’s note: 4-601.11(c): worn caulking with black mold like substance noted around base of 3-compartment sink. Instd to repair and maintain

      Official wording (code 49)

      Non-food/food contact surfaces clean

    • GeneralFacility upkeep

      Plumbing problems, or missing protection against backflow.

      Inspector’s note: 5-205.15: 3-compartment sink faucet leaking. Instd to repair and maintain

      Official wording (code 51)

      Plumbing installed; proper backflow devices

  11. Fail

    Canvass · Fail

    3 general Show violations
    • GeneralFacility upkeep

      Equipment and surfaces were dirty.

      Inspector’s note: Worn caulking with black mold like substance noted around base of 3-compartment sink. Instd to repair and maintain.

      Official wording (code 49)

      Non-food/food contact surfaces clean

    • GeneralFacility upkeep

      Plumbing problems, or missing protection against backflow.

      Inspector’s note: 3-compartment sink faucet leaking. Instd to repair and maintain.

      Official wording (code 51)

      Plumbing installed; proper backflow devices

    • GeneralFacility upkeep

      Garbage wasn’t handled or stored properly.

      Inspector’s note: Premises using large open dumpster without any lids, to dispose of materials containing food residue and refuse. Instd to provide receptacles designed and constructed to have tight fitting lids. Priority foundation 7-38-020(b).

      Official wording (code 54)

      Garbage & refuse properly disposed; facilities maintained

  12. Pass

    Canvass Re-Inspection · Pass

    8 general Show violations
    • GeneralMinor (pre-2018 form)

      Clean multi-use utensils and single service articles properly stored: no reuse of single service articles

      Inspector’s note: Inspector Comments: MUST INVERT MULTIUSE UTENSILS ON DISH STORAGE SHELF.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: Inspector Comments: MUST REPAIR OR REPLACE DAMAGED LID ON MILK COOLER ON SERVING LINE.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Inspector Comments: MUST CLEAN DUST BUILD UP FROM FANGUARD COVERS IN VEGETABLE WALK IN COOLER,LOWER SHELF OF STEAM TABLES,SOME SHELVING UNITS IN PRE-K 002.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Inspector Comments: MUST CLEAN DEBRIS FROM FLOOR IN VEGETABLE WALK IN COOLER AND SPILL ON FLOOR IN MILK WALK IN COOLER.MUST REPAIR OR REPLACE DAMAGED FLOOR TILES IN LUNCHROOM AND FLOORING PREP AREA BEHIND AND IN FRONT OF COOKING EQUIPMENT.MUST REMOVE RUST FROM FLOOR IN VEGETABLE WALK IN COOLER.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Inspector Comments: MUST REPLACE PUSHED BACK CEILING TILES OVER COOLERS IN PREP AREA.

    • GeneralMinor (pre-2018 form)

      Lighting: required minimum foot-candles of light provided, fixtures shielded

      Inspector’s note: Inspector Comments: MUST REPAIR OR REPLACE LOOSE LIGHT FIXTURE ABOVE SERVING LINE,BURNTOUT LIGHTS IN LUNCHROOM.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Inspector Comments: MUST ADJUST FAUCET HANDLES TO STAY ON LONGER IN ALL STUDENTS TOILETROOMS

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Inspector Comments: MUST ELEVATE,REMOVE OR ORGANIZE ARTICLES OFF OF FLOOR IN PRE-K OO1 & 002 CLOSETS.

  13. Fail

    Canvass · Fail

    9 general Show violations
    • GeneralSerious (pre-2018 form)

      No evidence of rodent or insect outer openings protected/rodent proofed, a written log shall be maintained available to the inspectors

      Inspector’s note: Observed evidence of appx. 30 or more rodent droppings on floor under shelving units and behind door in paper goods storage area and lower cabinet in lunchoom.also appx."1/2-3/4" gap along bottom and around locks on doors delivery,lunchroom,north,boilerroom,#10.must remove droppings clean and sanitize areas.rodent proof doors.recommended to have a pest control operator to service premises on or after 3/14/18.(no citation issued)

    • GeneralMinor (pre-2018 form)

      Clean multi-use utensils and single service articles properly stored: no reuse of single service articles

      Inspector’s note: Must invert multiuse utensils on dish storage shelf.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: Must repair or replace damaged lid on milk cooler on serving line.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Must clean dust build up from fanguard covers in vegetable walk in cooler,lower shelf of steam tables,some shelving units in pre-k 002.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Must clean debris from floor in vegetable walk in cooler and spill on floor in milk walk in cooler.must repair or replace damaged floor tiles in lunchroom and flooring prep area behind and in front of cooking equipment.must remove rust from floor in vegetable walk in cooler.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Must replace pushed back ceiling tiles over coolers in prep area.

    • GeneralMinor (pre-2018 form)

      Lighting: required minimum foot-candles of light provided, fixtures shielded

      Inspector’s note: Must repair or replace loose light fixture above serving line,burntout lights in lunchroom.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Must adjust faucet handles to stay on longer in all students toiletrooms.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Must elevate,remove or organize articles off of floor in pre-k oo1 & 002 closets.

  14. Pass

    Canvass · Pass

    3 general Show violations
    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: Observed water on floor from cold holding milk refrigeration unit at serving line. Must repair.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Remove water on floor around cold holding milk refrigeration unit at serving line, keep floor dry at all times. Clean floor under shelving in produce walk-in cooler of food debris.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Remove clutter in first floor mop sink closet, organize and maintain at all times.

  15. Pass

    Canvass Re-Inspection · Pass

    4 general Show violations
    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Clean the massive dirt, dust, and debris from floors throughout all sections of the boiler room.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Seal all openings in walls around flush buttons above urinals and toilets in student washrooms where present. Seal loose base board in pre-k classroom 002. Replace all stained ceiling tiles in all student washrooms where present. Cleean debris and stains from ceiling tiles in student washrooms where present. Clean debris and dirt from light shields in hallways where present.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Repair faucets in the following areas: at wahbowl in 3rd flr boy's washroom, wahbowl in 4th flr boy's washroom, and 2 wash bowls in 2nd flr girls washroom. Repair 2 broken toilets in 3rd flr girl's washroom, and broken toilet in the 4th flr boy's washroom.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Eliminate clutter in all mop sink closets and throughout all sections of the boiler room. All articles stored throughout boiler room, in storage area in teacher's lounge, in pre-k classrom 001 and in mop sink closets must be properly stored elevated 6 inches off the floors

  16. Fail

    Canvass · Fail

    5 general Show violations
    • GeneralSerious (pre-2018 form)

      No evidence of rodent or insect outer openings protected/rodent proofed, a written log shall be maintained available to the inspectors

      Inspector’s note: Improper pest control and outer openings not protected noted on premises. North entrance left-center entry/exit door has a gap greater than 1/4 inch at left lower corner of the door. Must repair making door tight-fitting to prevent rodent entry. Also observed mice droppings 30 on floor inside boiler room underneath the ats box, and on floor near area where rock salt is stored. Must clean and sanitize all affected areas. Serious violation 7-38-020.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Clean the massive dirt, dust, and debris from floors throughout all sections of the boiler room.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Seal all openings in walls around flush buttons above urinals and toilets in student washrooms where present. Seal loose base board in pre-k classroom 002. Replace all stained ceiling tiles in all student washrooms where present. Cleean debris and stains from ceiling tiles in student washrooms where present. Clean debris and dirt from light shields in hallways where present.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Repair faucets in the following areas: at wahbowl in 3rd flr boy's washroom, wahbowl in 4th flr boy's washroom, and 2 wash bowls in 2nd flr girls washroom. Repair 2 broken toilets in 3rd flr girl's washroom, and broken toilet in the 4th flr boy's washroom.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Eliminate clutter in all mop sink closets and throughout all sections of the boiler room. All articles stored throughout boiler room, in storage area in teacher's lounge, in pre-k classrom 001 and in mop sink closets must be properly stored elevated 6 inches off the floors.

  17. Pass

    Canvass · Pass

    1 general Show violations
    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Must correct the following plumbing violations in the student washrooms: first floor boys has one handsink with no hot running water and first floor girls has one with no cold running water. Second floor boys middle sink has a broken cold water knob and no cold running water; replace knob and restore cold water to this sink. One toilet not working; repair toilet. Third floor boys has one sink with no running water; restore water at first sink.

  18. Pass

    Canvass · Pass

    6 general Show violations
    • GeneralMinor (pre-2018 form)

      Clean multi-use utensils and single service articles properly stored: no reuse of single service articles

      Inspector’s note: Multi-use utensils improperly stored. Instd to store properly (handle up).

    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: Worn caulking at base of 3-compartment sink and wall. Instd to remove and/or replace same.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Floor in corners of prep area not clean, with excessive paint spills. Instd to repair same.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Missing ceiling tiles in boys main and 1st floor toilet room. Replace same. Replace all stained ceiling tiles in all students toilet rooms. Lightshields not clean in prep area and student toilet rooms. Instd to clean same.

    • GeneralMinor (pre-2018 form)

      Lighting: required minimum foot-candles of light provided, fixtures shielded

      Inspector’s note: Lightshield missing in walk-in freezer. Provide same.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: All staff toilet room handsink faucets inadequate. Instd to repair same so as to provide adequate supply of hot/cold running water under city pressure without constant pressure of hand on faucet.

  19. Pass

    Canvass · Pass

    4 general Show violations
    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: The walk in milk cooler has dirty floors, clean, rinse and sanitize the floors from corner to corner.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: The walls in room 106 and the 2nd level hallway have peeling paint and damaged plaster in the coat closet area, repair damaged walls and pelling paint.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: The following plumbing fixtures are damaged or out of repair, 1st flr boys toilet 1st flr - 2nd level girls and boys toilets (one in each), 2nd flr - 3rd level boys urinal, and the boiler room mop sink. Repair the plumbing to code. Alternate fixtures are available throughout the building.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: The mdf room is dusty and cluttered, clean the room out and maintain it. The custodians mop closets have unlabeled non-toxic cleaning supplies in spray bottles,;

  20. Pass

    Canvass · Pass

    2 general Show violations
    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Seal openings around pipes of toilets in gitls washrooms on main and second level where needed. Replace stained or missing ceiling tile where needed in building. Scrape and remove peeling paint from walls of utility closets where needed.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Second floor boys middle handsink has no cold running water; restore. Replace missing hot water faucet knob in boys washroom at middle sink on third floor.

  21. Pass

    Canvass · Pass

    7 general Show violations
    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: All food and non-food contact equipment and utensils shall be smooth, easily cleanable, and durable, and shall be in good repair.MUST REPAIR OR REPLACE MISSING SIGNS ON ALL TOILET ROOM DOORS ,MISSING STALL DOOR & FRAME IN 2ND & 3RD FL. GIRL'S.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: All food and non-food contact surfaces of equipment and all food storage utensils shall be thoroughly cleaned and sanitized daily.MUST CLEAN SHELVING UNITS IN BOTH PRE-K CLASS ROOMS,MEAT SLICER.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair.MUST REPAIR OR REPLACE DAMAGED & MISSING FLOOR TILES IN LUNCH ROOM,MAIN FLOOR TOILET ROOMS FOR STAFF NEXT TO GYM,PRE-K #001 & BOILER ROOM TOILET ROOM.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: The walls and ceilings shall be in good repair and easily cleaned.MUST REPAIR OR REPLACE DAMAGED & MISSING WALL BASES IN MAIN FL.(W) TOILET ROOM NEXT TO GYM,STAINED & MISSING CEILING TILES IN MAIN FL.(G&B),1ST FL.(B&G),2ND & 3 FL.(G).MUST SCRAPE & PAINT PEELING PAINT ON WALLS IN MAIN FL.(M),PRE-K#002.MUST ADJUST DOOR SWEEPS ON NORTH & NORTHEAST DOORS.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health.MUST ADJUST FAUCET HANDLES AT SOME HAND SINKS IN TOILET ROOMS.MUST REPAIR OR REPLACE HAND SINKS & TOILETS IN TOILET ROOMS IN POOR REPAIR MAIN FL.(G),1ST FL.(G),2ND FL. (B),3RD FL. MOP SINK LEAKY FAUCET.

    • GeneralMinor (pre-2018 form)

      Refrigeration and metal stem thermometers provided and conspicuous

      Inspector’s note: All food establishments that display, prepare, or store potentially hazardous foods shall have calibrated metal stem thermometers, provided and conspicuous, for refrigerated and hot food units.HOT HOLDING CABINET NEEDS THERMOMETER.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: All parts of the food establishment and all parts of the property used in connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors.MUST ELEVATE ARTICLES OFF OF FLOOR & AWAY FROM WALLS IN M.D.F. ROOM,ELECTRICAL ROOM.

  22. Pass

    Canvass · Pass

    5 general Show violations
    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: All food and non-food contact equipment and utensils shall be smooth, easily cleanable, and durable, and shall be in good repair. MUST REPAIR BROKEN GASKET ON PREP COOLER DOOR IN KITCHEN.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair. MUST CLEAN FLOORS; THRU-OUT PRE-K CLASSROOM #002 AND BOILER ROOM.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: The walls and ceilings shall be in good repair and easily cleaned. MUST REPLACE DAMAGED CEILING PANELS INSIDE BOYS WASHROOM 1ST AND 2ND FLOORS, SEAL OPENINGS INSIDE PRE-K WASHROOM, ROOM #001 AND REMOVE PEELING PAINT INSIDE PRE-K CLASSROOM #002 CLOSET.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health MUST REPAIR FAUCETS INSIDE 1ST & 2ND FLOOR GIRLS WASHROOMS, INSIDE PRE-K #001 WASHROOM AND ALSO REPAIR LEAKING PIPES UNDER HAND BOWL SAME WASHROOM.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Must clean and organize boiler room and storage rooms, articles must be stored off floors away from walls to prevent pest harborage.

  23. Pass

    Suspected Food Poisoning · Pass

    4 general Show violations
    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair. MUST CLEAN FLOORS THRU-OUT BASEMENT/BOILER ROOM AND INSIDE MOP CLOSET AT 4TH FLOOR.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: The walls and ceilings shall be in good repair and easily cleaned. MUST SEAL OPENINGS INSIDE MOP CLOSET AT 4TH FLOOR BOY WASHROOM, AND SEAL RAW WOOD DOOR INSIDE 2ND FLOOR GIRLS WASHROOM.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. MUST REPAIR LEAKING PIPES IN BOILER ROOM.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Must remove unnecessary articles thru-out basement/boiler room, clean and organize to prevent pest harborage. Articles must be stored off floors, away from walls.

  24. Pass

    Canvass · Pass

    4 general Show violations
    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair. MUST CLEAN FLOORS THRU-OUT BASEMENT/BOILER ROOM AND INSIDE MOP CLOSET AT 4TH FLOOR.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: The walls and ceilings shall be in good repair and easily cleaned. MUST SEAL OPENINGS INSIDE MOP CLOSET AT 4TH FLOOR BOY WASHROOM, AND SEAL RAW WOOD DOOR INSIDE 2ND FLOOR GIRLS WASHROOM

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. MUST REPAIR LEAKING PIPES IN BOILER ROOM.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Must remove unnecessary articles thru-out basement/boiler room, articles must be stored off floors, away from walls.