Pass

Anton Dvorak Elementary

3615 W 16th St (1600S), Chicago, IL 60623

School ZIP 60623 Risk 1 (High)

Passed · as of Jan 20, 2026

Anton Dvorak Elementary was last inspected on January 20, 2026 with a result of “Pass”. Inspectors found 6 violations, 1 of them critical.

Latest inspection

January 20, 2026 · Canvass

Pass

Result: Pass

1 critical5 general
  • CriticalHygiene & sanitation

    Hand sinks were missing, blocked, or not stocked with soap and towels.

    Inspector’s note: Observed timed faucets not functioning properly at hand washing sinks in pre-k 103, pre-k 110, women first floor washroom near cafeteria, boys third floor washroom. Water must run continuously for at least 15 seconds before reactivating faucet.

    Official wording (code 10)

    Adequate handwashing sinks properly supplied and accessible

  • GeneralFacility upkeep

    Plumbing problems, or missing protection against backflow.

    Inspector’s note: Observed no hot water at 1-compartment sinks in pre-k 103 classroom. Instructed manager to repair and maintain.

    Official wording (code 51)

    Plumbing installed; proper backflow devices

  • GeneralFacility upkeep

    Toilet rooms weren’t built, stocked, or cleaned properly.

    Inspector’s note: Observed no covered receptacle in lunchroom staff office washroom. Instructed manager to provide covered receptacle inside washroom.

    Official wording (code 53)

    Toilet facilities: properly constructed, supplied, & cleaned

  • GeneralFacility upkeep

    Floors, walls, or ceilings were damaged or dirty.

    Inspector’s note: Observed peeling paint in ceiling above prep table near oven, water-stained ceiling tiles in small lunchroom area, missing and stained ceiling tiles above door in pre-k 110 classroom, openings around electrical outlet in lunchroom, and near piano in small lunchroom area. Instructed manager to repair and maintain.

    Official wording (code 55)

    Physical facilities installed, maintained & clean

  • GeneralFacility upkeep

    Floors, walls, or ceilings were damaged or dirty.

    Inspector’s note: Observed debris on floors along walls and corners in prep and storage areas, dust buildup on ceiling vents in lunchroom and washroom areas. Instructed manager to clean and maintain.

    Official wording (code 55)

    Physical facilities installed, maintained & clean

  • GeneralFacility upkeep

    Ventilation or lighting was inadequate.

    Inspector’s note: Observed missing light shield inside display case in serving area. Instructed manager to provide light shield or shatterproof bulb.

    Official wording (code 56)

    Adequate ventilation & lighting; designated areas used

Inspection history

33 inspections on record

  1. Pass

    Canvass Re-Inspection · Pass

    1 general Show violations
    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Observed floors in additional room where cooling units are stored in need of cleaning as well as book room. Instructed to remove all food and miscellaneous debris.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

  2. Fail

    Canvass · Fail

    1 critical1 general Show violations
    • CriticalHygiene & sanitation

      Hand sinks were missing, blocked, or not stocked with soap and towels.

      Inspector’s note: Observed washbowls located inside pre-k classroom toilet rooms, boys 2nd floor and girls near book room on 1st floor without hot running water near book room instructed to provide and maintain at least @100f. Instructed to repair. Priority violation.

      Official wording (code 10)

      Adequate handwashing sinks properly supplied and accessible

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Observed floors in additional room where cooling units are stored in need of cleaning as well as book room. Instructed to remove all food and miscellaneous debris.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

  3. Pass

    Canvass Re-Inspection · Pass

    5 general Show violations
    • GeneralPests

      Insects, rodents, or animals were present, or the building wasn’t sealed against them.

      Inspector’s note: 6-202.15 observed the rear door of the facility attached to the kitchen, not rodent proof. Instructed to provide n order to prevent pest entry.

      Official wording (code 38)

      Insects, rodents, & animals not present

    • GeneralFacility upkeep

      Plumbing problems, or missing protection against backflow.

      Inspector’s note: 5-205.15 observed 1 out of 4 stalls in the 2nd floor girls' toilet room inoperable and not flushing. Instructed to repair and maintain in good condition.

      Official wording (code 51)

      Plumbing installed; proper backflow devices

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: 6-501.13 observed food excessive food debris behind the stove in the prep area as well as in the corner underneath the dishwasher. Instructed to remove.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: 6-201.11 observed broken floor tiles in front of the stove in the prep area. Instructed to replace and provide smooth and easily cleanable.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

    • GeneralFacility upkeep

      Ventilation or lighting was inadequate.

      Inspector’s note: 6-303.11 observed inadequate lighting in the prep area. Instructed to provide.

      Official wording (code 56)

      Adequate ventilation & lighting; designated areas used

  4. Fail

    Canvass · Fail

    7 general1 paperwork Show violations
    • GeneralPests

      Insects, rodents, or animals were present, or the building wasn’t sealed against them.

      Inspector’s note: Observed approximately 15 large rodent droppings behind the stove in the prep area during the time of inspection. Instructed to remove and sanitize said area. Must eliminate pest activity on the premises. Priority foundation violation. 7-38-020 (a). No citation issued.

      Official wording (code 38)

      Insects, rodents, & animals not present

    • GeneralPests

      Insects, rodents, or animals were present, or the building wasn’t sealed against them.

      Inspector’s note: Observed rear door of the facility attached to kitchen not rodent proof. Instructed to provide n order to prevent pest entry.

      Official wording (code 38)

      Insects, rodents, & animals not present

    • GeneralFacility upkeep

      Plumbing problems, or missing protection against backflow.

      Inspector’s note: Observed 1 out of 4 stalls in 2nd floor girls' toilet room inoperable and not flushing. Instructed to repair and maintain in good condition.

      Official wording (code 51)

      Plumbing installed; proper backflow devices

    • GeneralFacility upkeep

      Garbage wasn’t handled or stored properly.

      Inspector’s note: Observed lids not tight fitted on outside receptacle with garbage overflowing. Instructed to provide a receptacle with tight fitted lid to prevent pest harborage. Priority foundation violation. #7-38-020 (b). No citation issued.

      Official wording (code 54)

      Garbage & refuse properly disposed; facilities maintained

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Observed food excessive food debris behind the stove in the prep area as well as in the corner underneath the dishwasher. Instructed to remove.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Observed broken floor tiles in front of the stove in the prep area. Instructed to replace and provide smooth and easily cleanable.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

    • GeneralFacility upkeep

      Ventilation or lighting was inadequate.

      Inspector’s note: Observed inadequate lighting in the prep area. Instructed to provide.

      Official wording (code 56)

      Adequate ventilation & lighting; designated areas used

    • PaperworkManagement & training

      No manager on duty held a City of Chicago food sanitation certificate.

      Inspector’s note: Observed no city of chicago certified food manager on site during the time of inspection while preparing and serving dairy. Noted expired certificates posted. Instructed to provide at least one cfm with valid original certificate. Priority foundation violation. #7-38-012. No citation issued.

      Official wording (code 2)

      City of chicago food service sanitation certificate

  5. Pass

    Canvass · Pass

    3 general Show violations
    • GeneralFacility upkeep

      Toilet rooms weren’t built, stocked, or cleaned properly.

      Inspector’s note: Observed no covered waste receptacle in staff washroom. Instructed to provide and maintain.

      Official wording (code 53)

      Toilet facilities: properly constructed, supplied, & cleaned

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Observed peeling paint on ceiling in kitchen. Instructed manager to repair and maintain.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Instructed to clean the ceiling vent in the kitchen washroom for employees to remove heavy dust build up.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

  6. Pass

    Canvass · Pass

    1 critical3 general Show violations
    • CriticalHygiene & sanitation

      Hand sinks were missing, blocked, or not stocked with soap and towels.

      Inspector’s note: Observed some faucets in student washrooms did not run for 15 seconds; instructed to adjust faucets to run for 15 seconds when in use.

      Official wording (code 10)

      Adequate handwashing sinks properly supplied and accessible

    • GeneralFacility upkeep

      Toilet rooms weren’t built, stocked, or cleaned properly.

      Inspector’s note: Observed some female staff and female student washroom waste receptacles without covers; must provide as required.

      Official wording (code 53)

      Toilet facilities: properly constructed, supplied, & cleaned

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Observed peeling paint on the ceiling of the mens washroom on the first floor near the lunchroom and on the ceiling of the boys wasrhooms on the first and second floor; instructed to remove peeling paint. Observed peeling paint on the kitchen ceiling over the steamer, kitchen ceiling over a prep table and kitchen ceiling by the side door exit sign; remove peeling paint from areas.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Instructed to clean the ceiling vent in the kitchen washroom for employees to remove heavy dust build up.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

  7. Pass

    Canvass Re-Inspection · Pass

    5 general Show violations
    • GeneralFood handling

      Clean utensils, equipment, or linens weren’t stored and handled properly.

      Inspector’s note: 4-903.11 (A;B;D) Inspector Comments: OBSERVED MUTLIUSE UTENSILS STORED IMPROPERLY IN KITCHEN. MUST INVERT MULTIUSE UTENSILS WITH HANDLES IN UPRIGHT POSITION.

      Official wording (code 44)

      Utensils, equipment & linens: properly stored, dried, & handled

    • GeneralFacility upkeep

      Equipment or surfaces were in poor repair or made of material that can’t be cleaned.

      Inspector’s note: 4-501.11 Inspector Comments: OBSERVED TORN/DAMAGED RUBBER GASKET ON DOORS OF REACH-IN COOLERS IN KITCHEN AREA. INSTRUCTED TO REPAIR OR REPLACE GASKET.

      Official wording (code 47)

      Food & non-food contact surfaces cleanable, properly designed, constructed & used

    • GeneralFacility upkeep

      Toilet rooms weren’t built, stocked, or cleaned properly.

      Inspector’s note: 5-501.17 Inspector Comments: OBSERVED NO COVERED WASTE RECEPTACLE IN STAFF WASHROOM. INSTRUCTED TO PROVIDE AND MAINTAIN.

      Official wording (code 53)

      Toilet facilities: properly constructed, supplied, & cleaned

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: 6-501.11 Inspector Comments: OBSERVED PEELING PAINT ON CEILING IN KITCHEN. INSTRUCTED MANAGER TO REPAIR AND MAINTAIN.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: 6-501.114 Inspector Comments: OBSERVED UNUSED EQUIPMENT AND UNNECESSARY ARTICLES IN KITCHEN AREA. INSTRUCTED MANAGER TO REMOVE ALL UNUSED, UNNECSSARY EQUIPMENT AND ARTICLES TO PREVENT PEST HARBORAGE.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

  8. Fail

    Canvass · Fail

    1 critical6 general Show violations
    • CriticalManagement & training

      No written plan or kit for cleaning up vomit or diarrhea.

      Inspector’s note: Observed no adequate supplies on site to properly respond to vomit and/or diarrheal events that can potentially occur inside of the facility. Instructed to provide. Priority foundation 7-38-005.

      Official wording (code 5)

      Procedures for responding to vomiting and diarrheal events

    • GeneralPests

      Insects, rodents, or animals were present, or the building wasn’t sealed against them.

      Inspector’s note: Observed mice droppings on floor in storage/reach in cooler room next to kitchen. Instructed manager to clean and sanitize all areas. Priority foundation 7-38-020 (a).

      Official wording (code 38)

      Insects, rodents, & animals not present

    • GeneralFood handling

      Clean utensils, equipment, or linens weren’t stored and handled properly.

      Inspector’s note: Observed mutliuse utensils stored improperly in kitchen. Must invert multiuse utensils with handles in upright position.

      Official wording (code 44)

      Utensils, equipment & linens: properly stored, dried, & handled

    • GeneralFacility upkeep

      Equipment or surfaces were in poor repair or made of material that can’t be cleaned.

      Inspector’s note: Observed torn/damaged rubber gasket on doors of reach-in coolers in kitchen area. Instructed to repair or replace gasket.

      Official wording (code 47)

      Food & non-food contact surfaces cleanable, properly designed, constructed & used

    • GeneralFacility upkeep

      Toilet rooms weren’t built, stocked, or cleaned properly.

      Inspector’s note: Observed no covered waste receptacle in staff washroom. Instructed to provide and maintain.

      Official wording (code 53)

      Toilet facilities: properly constructed, supplied, & cleaned

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Observed unused equipment and unnecessary articles in kitchen area. Instructed manager to remove all unused, unnecssary equipment and articles to prevent pest harborage.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Observed peeling paint on ceiling in kitchen. Instructed manager to repair and maintain.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

  9. Pass

    Canvass Re-Inspection · Pass

    2 general Show violations
    • GeneralFacility upkeep

      Toilet rooms weren’t built, stocked, or cleaned properly.

      Inspector’s note: 5-501.17 observed no closed receptacles inside of the employee's and girls toilet rooms. Instructed to provide.

      Official wording (code 53)

      Toilet facilities: properly constructed, supplied, & cleaned

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: 6-201.11 observed some peeling paint on the ceiling above the prep tables in the food prep area. Instructed to make the surface smooth and easily cleanable.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

  10. Fail

    Canvass · Fail

    1 critical4 general Show violations
    • CriticalHygiene & sanitation

      Hand sinks were missing, blocked, or not stocked with soap and towels.

      Inspector’s note: 5-202.12(a) observed no hot water at the hand washing sink located in the toilet rooms of pre-k rooms 101 and 103. Instructed to provide adequate hot water at said hand washing sinks. Hot water should maintain 100f at all times. Priority violation 7-38-030(c).

      Official wording (code 10)

      Adequate handwashing sinks properly supplied and accessible

    • GeneralPests

      Insects, rodents, or animals were present, or the building wasn’t sealed against them.

      Inspector’s note: 6-501.111 observed evidence of rodent activity. Observed about 5 rodent droppings under the dish machine in the food prep area, about 30 rodent droppings under the one compartment sink in the pre-k classroom room 101 and about 10 rodent droppings along the walls also in room 101. Observed about 30 rodent droppings located in a closet in the pre-k room 103 and about 10 rodent droppings located along the walls also in room 103. Instructed to clean and sanitized the affected areas and recommended contaacting pest control for a service. Priority foundation 7-38-020(a).

      Official wording (code 38)

      Insects, rodents, & animals not present

    • GeneralFacility upkeep

      Toilet rooms weren’t built, stocked, or cleaned properly.

      Inspector’s note: 5-501.17 observed no closed receptacles inside of the employee's and girls toilet rooms. Instructed to provide.

      Official wording (code 53)

      Toilet facilities: properly constructed, supplied, & cleaned

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: 6-201.11 observed some peeling paint on the ceiling above the prep tables in the food prep area. Instructed to make the surface smooth and easily cleanable.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: 6-501.114 observed items on the floor in the pre-k rooms. Instructed to elevate everything or remove unnecessary items.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

  11. Conditional

    Canvass · Pass w/ Conditions

    1 critical1 general Show violations
    • CriticalManagement & training

      No written plan or kit for cleaning up vomit or diarrhea.

      Inspector’s note: No procedure/supplies in place for responding to vomiting and diarrheal events. Instd to provide procedure/supplies and verify that disinfectant is effective against virus including norovirus. Priority foundation 7-38-010.

      Official wording (code 5)

      Procedures for responding to vomiting and diarrheal events

    • GeneralFacility upkeep

      Floors, walls, or ceilings were damaged or dirty.

      Inspector’s note: Peeling paint on ceiling in prep area. Instd to repair and maintain surface smooth, even, and easily cleanable.

      Official wording (code 55)

      Physical facilities installed, maintained & clean

  12. Pass

    Canvass Re-Inspection · Pass

    3 general Show violations
    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Inspector Comments: Inspector Comments: MUST CLEAN FOOD DEBRIS FROM MILK COOLERS,STAFF LOUNGE-LOWER CABINETS,COUNTER TOPS.PRE-K ROOMS 101 & 103 DUST BUILD UP ON SOME SHELVING UNITS,CUBBIES & WINDOW SILLS.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Inspector Comments: Inspector Comments: MUST REPAIR OR REPLACE STAINED CEILING TILES IN DRY FOOD STORAGE AREA,PRE-K ROOM 101 & 103.LUNCHROOM -LOOSE WALL BASES.MUST SCRAPE AND PAINT PEELING PAINT ON CEILING IN PREP AREA.MUST CLEAN DIRT BUILD UP ON WALLS IN LUNCHROOM.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Inspector Comments: Inspector Comments: MUST ADJUST FAUCET HANDLES TO STAY ON LONGER AT HAND SINKS IN 3RD FL. STAFF & BOY'S TOILETROOMS.

  13. Fail

    Canvass Re-Inspection · Fail

    5 general Show violations
    • GeneralSerious (pre-2018 form)

      No evidence of rodent or insect outer openings protected/rodent proofed, a written log shall be maintained available to the inspectors

      Inspector’s note: Inspector Comments: STILL APPX."1/2-3/4" GAP ALONG BOTTOM OF DOOR GYM.MUST RODENT PROOF DOOR.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Inspector Comments: MUST CLEAN FOOD DEBRIS FROM MILK COOLERS,STAFF LOUNGE-LOWER CABINETS,COUNTER TOPS.PRE-K ROOMS 101 & 103 DUST BUILD UP ON SOME SHELVING UNITS,CUBBIES & WINDOW SILLS.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Inspector Comments: MUST CLEAN FOOD DEBRIS FROM FLOOR UNDER,AROUND,ALONG WALL BASES IN PREP AREA.MUST SEAL HOLE IN FLOOR NEAR RADIATOR IN DRY FOOD STORAGE AREA.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Inspector Comments: MUST REPAIR OR REPLACE STAINED CEILING TILES IN DRY FOOD STORAGE AREA,PRE-K ROOM 101 & 103.LUNCHROOM -LOOSE WALL BASES.MUST SCRAPE AND PAINT PEELING PAINT ON CEILING IN PREP AREA.MUST CLEAN DIRT BUILD UP ON WALLS IN LUNCHROOM.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Inspector Comments: MUST ADJUST FAUCET HANDLES TO STAY ON LONGER AT HAND SINKS IN 3RD FL. STAFF & BOY'S TOILETROOMS.

  14. Fail

    Canvass · Fail

    1 critical7 general Show violations
    • CriticalCritical (pre-2018 form)

      Adequate number, convenient, accessible, designed, and maintained

      Inspector’s note: Observed hand washing facilities for kitchen staff not maintained.observed no cold running water at hand sink in food prep/dish washing area.must provide cold and hot running water under city pressure at all times.cold running water was restored at hand sink during inspection(no citation issued)

    • GeneralSerious (pre-2018 form)

      No evidence of rodent or insect outer openings protected/rodent proofed, a written log shall be maintained available to the inspectors

      Inspector’s note: Observed evidence of appx. 40 or more rodent droppings on floor in food prep area-behind oven.pre-k room 103 -on floor next to cubbies,closet storage shelves,lower shelf under hand sink.pre-k room 101-on floor next to cubbies,storage closet and cabinet.also.evidence of 1- live roach crawling on floor behind milk cooler in dry food storage area.appx.50 or more live small flies flying around,on walls in prep/dish washing area,dry food storage area,lunchroom,pre-k room 103.appx."1/2-3/4" gap along bottom of doors # 6,7.prep area,gym,boiler room.must remove droppings clean and sanitize areas.rodent proof doors.recommended to have a pest control operator to service premises on or after 4/12/18.(no citation issued)

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Must clean food debris from milk coolers,staff lounge-lower cabinets,counter tops.pre-k rooms 101 & 103 dust build up on some shelving units,cubbies & window sills.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Must clean food debris from floor under,around,along wall bases in prep area.must seal hole in floor near radiator in dry food storage area.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Must repair or replace stained ceiling tiles in dry food storage area,pre-k room 101 & 103.lunchroom -loose wall bases.must scrape and paint peeling paint on ceiling in prep area.must clean dirt build up on walls in lunchroom.

    • GeneralMinor (pre-2018 form)

      Lighting: required minimum foot-candles of light provided, fixtures shielded

      Inspector’s note: Must replace burnt out light in staff lounge,missing light shield in pre-k room 101.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Must adjust faucet handles to stay on longer at hand sinks in 3rd fl. Staff & boy's toiletrooms.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Must elevate,remove and organize articles off of floor and away from walls in pre- k rooms 101 & 103.

  15. Pass

    Canvass · Pass

    3 general Show violations
    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Floors not clean in various areas, dining areas, bathrooms and 3rd floor storage area, instructed to detail clean and better maintain,

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Ceiling tile in small dining area badly stained, instructed to replace,

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Clutter in storage rooms 1st and 3rd floor areas, instructed to clean and better organize all storage areas,

  16. Pass

    Canvass Re-Inspection · Pass

    2 general Show violations
    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Massive dirt, dust and debris found on floors and rugs inside all pre-k and head start classrooms. These areas must be cleaned. Also found massive dirt, dust, and debris throughout all hallways, in both dining rooms, and inside kitchen prep area behind unused cooking stoves. All affected areas must be cleaned and sanitized.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Replace all stained ceiling tiles in the following areas: inside the small dining room inside the cafeteria, in kittchen prep area, and in head start classroom 101. Clean dust, debris and/or dead insects from light shields in the following areas: in 3rd floor hallway, and in student washrooms where present.

  17. Fail

    Canvass · Fail

    6 general Show violations
    • GeneralSerious (pre-2018 form)

      No evidence of rodent or insect outer openings protected/rodent proofed, a written log shall be maintained available to the inspectors

      Inspector’s note: Improper pest control noted on premises. 5 small flies observed in kitchen prep area. Also observed 30 mice droppings scattered on floor in boiler room between cluttered areas and along the bases of the walls. 30 roach droppings and roach castings also found along the bases of the walls in same room(unable to thoroughly inspect these areas due to the massive clutter). Must clean and sanitize all affected areas, seal up any opening in floors, walls, and ceilings, re-organize entire area by eliminating all clutter and request additional visit from pest control company(for both the kitchen and boiler room areas). Serious violation 7-38-020.

    • GeneralSerious (pre-2018 form)

      Outside garbage waste grease and storage area; clean, rodent proof, all containers covered

      Inspector’s note: Outside garbage area not properly maintained. Overflowing trash 10 inches above the rims noted in both dumpsters in the corral. Also found 2 lids missing off of one of the receptacles; must have this receptacle replaced and all lids must be kept closed on both containers. Massive debris also noted on ground inside corral which must be cleaned up. Serious violation 7-38-020.

    • GeneralSerious (pre-2018 form)

      Adequate number, convenient, accessible, properly designed and installed

      Inspector’s note: No hot water found at exposed hand sink in pre-k 103. Washroom in pre-k 103 not properly maintained. Huge puddles of water inside the washroom as well as on the floor inside the classroom and in the storage room used by the head start classroom next door. Children unable to use this facility. Must locate the source of the leak and make the necessary repairs. Serious violation 7-38-030.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Massive dirt, dust and debris found on floors and rugs inside all pre-k and head start classrooms. These areas must be cleaned. Also found massive dirt, dust, and debris throughout all hallways, in both dining rooms, and inside kitchen prep area behind unused cooking stoves. All affected areas must be cleaned and sanitized.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Replace all stained ceiling tiles in the following areas: inside the small dining room inside the cafeteria, in kittchen prep area, and in head start classroom 101. Clean dust, debris and/or dead insects from light shields in the following areas: in 3rd floor hallway, and in student washrooms where present.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Must clean the interior of the unused dish machine inside kitchen prep area, and have it serviced by pest control company( dead roaches and roach castings found inside).

  18. Pass

    Canvass · Pass

    3 general Show violations
    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: Found one rubber gasket at the two door cooler storing yogurt in the kitchen is loose on the right side; repair or replace gasket to avoid escaping air from unit.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Observed pieces of fruit and other items on the floor behind the stove; must clean floor behind stove in kitchen.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Observed peeling paint on the ceiling above the urinals in the boys washroom on the first floor; remove peeling paint and repaint area.

  19. Conditional

    Canvass Re-Inspection · Pass w/ Conditions

    1 critical8 general Show violations
    • CriticalCritical (pre-2018 form)

      Previous serious violation corrected, 7-42-090

      Inspector’s note: Previous serious violation from report #1385319 5/14/14 #18 not corrected.still observed evidence of more than 20 rodent droppings in pre-k 103 on floor in between file cabinets,on lower shelf of cubbies.pre-k 101 in lower cabinets at sink and on shelf at science area.also 2- live small flies on wall & boxes in prep area.no license in pest control logbook.north east door sweep worn.must remove droppings,clean & sanitize areas.rodent proof door.recommended to have a pest control operator to service premises on or after 5/21/14 and provide a copy of pest control license.(serious 7-38-020). Pest control operator arrived on site,droppings are now removed,pest control license provide,door sweep is repaired at this time of inspection.(critical 7-42-090).

    • GeneralSerious (pre-2018 form)

      No evidence of rodent or insect outer openings protected/rodent proofed, a written log shall be maintained available to the inspectors

      Inspector’s note: Violation not corrected see violation #14.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Inspector Comments: MUST CLEAN DUST BUILD UP FROM SOME CUBBIES & SHELVING UNITS IN PRE-K CLASSROOMS.MUST DEFROST FREEZER IN PRE-K 103.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Inspector Comments: MUST REPLACE MISSING FLOOR TILES IN STAFF LOUNGE.MUST CLEAN FLOOR IN BOILER ROOM,STORAGE ROOM117.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Inspector Comments: MUST REPLACE OR REPLACE STAINED CEILING TILES IN STAFF LOUNGE AREA,PRE-K 103 & 101,MISSING WALLTILES AT REAR DOOR IN KITCHEN

    • GeneralMinor (pre-2018 form)

      Lighting: required minimum foot-candles of light provided, fixtures shielded

      Inspector’s note: Inspector Comments: MUST REPLACE BURNOUT BULB IN PRE-K 103 CLOSET.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Inspector Comments: MUST ADJUST SOME FAUCETS AT HAND SINKS IN 1ST,2ND & 3RD FL. TOILET ROOMS.MUST REPAIR HAND DRYERS IN 1ST FL. BOY'S & GIRL'S

    • GeneralMinor (pre-2018 form)

      Refrigeration and metal stem thermometers provided and conspicuous

      Inspector’s note: Inspector Comments: MUST PROVIDE THERMOMETER FOR PRE-K 103 REFRIGERATOR.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Inspector Comments: MUST ELEVATE,ORGANIZE ARTICLES OFF OF FLOOR & AWAY FROM WALLS IN STORAGE ROOM 117,BOILER ROOM & PRE-K CLOSETS

  20. Fail

    Canvass · Fail

    8 general Show violations
    • GeneralSerious (pre-2018 form)

      No evidence of rodent or insect outer openings protected/rodent proofed, a written log shall be maintained available to the inspectors

      Inspector’s note: Observed evidence of more than 20 rodent droppings in pre-k 103 on floor in between file cabinets,on lower shelf of cubbies.pre-k 101 in lower cabinets at sink and on shelf at science area.also 6- live small flies on wall & boxes in prep area.no license in pest control logbook.north east door sweep worn.must remove droppings,clean & sanitize areas.rodent proof door.recommended to have a pest control operator to service premises on or after 5/14/14 and provide a copy of pest control license.(serious 7-38-020).

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Must clean dust build up from some cubbies & shelving units in pre-k classrooms.must defrost freezer in pre-k 103.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Must replace missing floor tiles in staff lounge.must clean floor in boiler room,storage room117.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Must replace or replace stained ceiling tiles in staff lounge area,pre-k 103 & 101,missing walltiles at rear door in kitchen.

    • GeneralMinor (pre-2018 form)

      Lighting: required minimum foot-candles of light provided, fixtures shielded

      Inspector’s note: Must replace burnout bulb in pre-k 103 closet.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Must adjust some faucets at hand sinks in 1st,2nd & 3rd fl. Toilet rooms.must repair hand dryers in 1st fl. Boy's & girl's.

    • GeneralMinor (pre-2018 form)

      Refrigeration and metal stem thermometers provided and conspicuous

      Inspector’s note: Must provide thermometer for pre-k 103 refrigerator.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Must elevate,organize articles off of floor & away from walls in storage room 117,boiler room & pre-k closets.

  21. Conditional

    Canvass · Pass w/ Conditions

    5 general Show violations
    • GeneralSerious (pre-2018 form)

      Food protected during storage, preparation, display, service and transportation

      Inspector’s note: The walk in cooler is dripping water from the condenser onto sealed containers and boxes of food in said cooler. The sealed food containers were sanitized with a 200 ppm solution of quaternary ammonia at this time. The cooler is tagged held for inspection until repaired and reinspected by the department of public health. The children in pre-k room # 101 were observed being fed in the class room with rusty metal utensils (spoons/forks) the teacher was instructed to discard said utensils at this time. The principle, chartwells supervisor and manager and cdph supervisor were notified. Any multi-use food serving utensil or tool used for food preparation or consumption must be smooth, sanitary, free from defects and be washed, rinsed and sanitized after every use.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: The refrigerators in the pre-k rooms are frosted up and dirty: defrost, wash, rinse and sanitize the refrigerators.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: The floors in the cafeteria (dolphin cafe) are dirty, clean the floors from corner to corner.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: The first floor boy's washroom has an out of order urinal, alternate urinals available, repair the urinal. The boiler room floor drain is full of buildup, clean out the floor drain.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: The caged in boiler room water line room is cluttered, remove unnecessary clutter so the area can be inspected.

  22. Pass

    Canvass Re-Inspection · Pass

    No violations

  23. Fail

    Canvass Re-Inspection · Fail

    1 critical5 general Show violations
    • CriticalCritical (pre-2018 form)

      No evidence of rodent or insect infestation, no birds, turtles or other animals

      Inspector’s note: Inspector Comments: PREVIOUS CRITICAL VIOLATION FROM REPORT #1170305 6/15/12 #13 STILL NOT CORRECTED.STILL FINDING EVIDENCE OF A INFESTATION OF MORE THAN 50 MOUSE DROPPINGS IN VARIOUS AREAS SUCH AS ON LEDGE OF STEAM TABLE AT SERVING LINE,ON FLOOR ALONG WALL BASES IN STAFF LOUNGE/REFRIGERATOR STORAGE ROOM,ADJACENT ROOM NEXT TO LUNCH ROOM ON FLOOR,IN CLOSET,PRE-K ROOM 103 UNDER HAND SINK CABINET,PRE-K 101 ON FLOOR AT RUG IN BOOK SHELF AREA, BOILER ROOM ON FLOOR ALONG WALL BASES.ALSO KITCHEN DOOR & SCREEN DOOR,NORTH EAST DOOR ARE NOT RODENT PROOFED.MUST REMOVE DROPPINGS,CLEAN & SANITIZE AREAS,RODENT PROOF DOORS.RECOMMENDED TO HAVE A PEST CONTROL OPERATOR TO SERVICE PREMISES ON OR AFTER 6/22/12.(CRITICAL 7-38-020).48 HOURS NOTICE.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: Inspector Comments: Inspector Comments: MUST REMOVE RUST FROM SHELVING UNITS IN WALK IN COOLER.MUST REPAIR OR REPLACE WORN DOOR GASKETS ON WALK IN COOLER.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Inspector Comments: Inspector Comments: MUST CLEAN ALL SHELVING UNITS,CUBBIES IN PRE-K 101 & 103.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Inspector Comments: MUST REPAIR OR REPLACE DAMAGED & MISSING FLOOR TILES IN STAFF LOUNGE/REFRIGERATOR STORAGE ROOM.MUST CLEAN FLOOR IN ELECTRIC ROOM

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Inspector Comments: MUST SCRAPE & PAINT PEELING PAINT ON WALL IN KITCHEN STAFF TOILET ROOM

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Inspector Comments: MUST REPAIR OR REPLACE LOW WATER PRESSURE AT HAND SINK IN PRE- K 103 TOILET ROOM

  24. Fail

    Canvass Re-Inspection · Fail

    1 critical5 general Show violations
    • CriticalCritical (pre-2018 form)

      No evidence of rodent or insect infestation, no birds, turtles or other animals

      Inspector’s note: Previous critical violation from report #1170301 6/13/12 #13 still not corrected.still finding evidence of a infestation of more than 100 mouse droppings in various areas such as on ledge of steam table at serving line,on floor along wall bases in staff lounge/refrigerator storage room,adjacent room next to lunch room on floor,in closet & shelving units,book storage room on shelving units,pre-k room 103 on toy shelves,under hand sink cabinet,pre-k 101 on floor at rug in book shelf area,electrical room & boiler room on floor along wall bases.also kitchen door & screen door,north east door are not rodent proofed.no current pest control license in log book.must remove droppings,clean & sanitize areas,rodent proof doors,provide license.recommended to have a pest control operator to service premises on or after 6/15/12.(critical 7-38-020).48 hours notice.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: Inspector Comments: MUST REMOVE RUST FROM SHELVING UNITS IN WALK IN COOLER.MUST REPAIR OR REPLACE WORN DOOR GASKETS ON WALK IN COOLER.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Inspector Comments: MUST CLEAN ALL SHELVING UNITS,CUBBIES IN PRE-K 101 & 103.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Inspector Comments: MUST REPAIR OR REPLACE DAMAGED & MISSING FLOOR TILES IN STAFF LOUNGE/REFRIGERATOR STORAGE ROOM.MUST CLEAN FLOOR IN ELECTRIC ROOM

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Inspector Comments: MUST SCRAPE & PAINT PEELING PAINT ON WALL IN KITCHEN STAFF TOILET ROOM

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Inspector Comments: MUST REPAIR OR REPLACE LOW WATER PRESSURE AT HAND SINK IN PRE- K 103 TOILET ROOM

  25. Fail

    Canvass · Fail

    1 critical5 general Show violations
    • CriticalCritical (pre-2018 form)

      No evidence of rodent or insect infestation, no birds, turtles or other animals

      Inspector’s note: Observed evidence of mouse droppings infestation throughout premises more than 200 in various areas such as ledge of stove,behind food storage cabinets,on floor outside of food managers office,behind reach in cooler,on ledges of steam table at serving line,on floor & on radiator covers in staff lounge/refrigerator storage room,adjacent room next to lunch room on floor,closet,shelving units,book storage room 117 on all shelving units,pre-k 103 on toy shelves,under sink cabinet,under table,pre-k 101 on floor behind book shelves,electrical room & boiler room on floor along wall bases.also kitchen door & screen door ,north east doors are not rodent proofed.also no current pest control license in log book.must remove droppings,clean & sanitize areas.rodent proof doors.recommended to have a pest control operator to service premises on or after 6/13/12.(critical 7-38-020)48 hours notice.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: Must remove rust from shelving units in walk in cooler.must repair or replace worn door gaskets on walk in cooler.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Must clean all shelving units,cubbies in pre-k 101 & 103.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Must repair or replace damaged & missing floor tiles in staff lounge/refrigerator storage room.must clean floor in electric room.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Must scrape & paint peeling paint on wall in kitchen staff toilet room.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Must repair or replace low water pressure at hand sink in pre- k 103 toilet room.

  26. Pass

    Canvass Re-Inspection · Pass

    6 general Show violations
    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Inspector Comments: Inspector Comments: Inspector Comments: All food and non-food contact surfaces of equipment and all food storage utensils shall be thoroughly cleaned and sanitized daily.MUST CLEAN ALL SHELVING UNITS & CUBBIES IN PRE-K 101 & 103,2ND FL. BOOK ROOM SHELVING UNITS.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Inspector Comments: Inspector Comments: Inspector Comments: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair.MUST REPAIR OR REPLACE DAMAGED & MISSING FLOOR TILES IN KITCHEN AT REAR DOOR,OPENING IN FLOOR ALONG WALL BASE IN ROOM 117.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Inspector Comments: Inspector Comments: Inspector Comments: The walls and ceilings shall be in good repair and easily cleaned.MUST SCRAPE & PAINT PEELING PAINT ON CEILING IN KITCHEN,WALL IN KITCHEN STAFF TOILET ROOM

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Inspector Comments: Inspector Comments: Inspector Comments: The flow of air discharged from kitchen fans shall always be through a duct to a point above the roofline.MUST REPAIR OR REPLACE 2ND FL. STAFF,PRE-K 103, LOW WATER PRESSURE.

    • GeneralMinor (pre-2018 form)

      Refrigeration and metal stem thermometers provided and conspicuous

      Inspector’s note: Inspector Comments: Inspector Comments: Inspector Comments: All food establishments that display, prepare, or store potentially hazardous foods shall have calibrated metal stem thermometers, provided and conspicuous, for refrigerated and hot food units.PRE-K 103 NEEDS THERMOMETER.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Inspector Comments: connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors.MUST ELEVATE & ORGANIZE ARTICLES OFF OF FLOOR & AWAY FROM WALLS IN PAPER STORAGE AREA,ROOM 117.

  27. Fail

    Canvass Re-Inspection · Fail

    8 general Show violations
    • GeneralSerious (pre-2018 form)

      Outside garbage waste grease and storage area; clean, rodent proof, all containers covered

      Inspector’s note: Inspector Comments: Inspector Comments: The area outside of the establishment used for the storage of garbage shall be clean at all times and shall not constitute a nuisance.OBSERVED OUTSIDE GARBAGE AREA NOT MAINTAINED GARBAGE CANS OVER FLOWING,LIDS WIDE OPEN,TRASH & DEBRI ON GROUND IN CORRAL,LIDS PUSHED DOWN INSIDE OF DUMPSTER.MUST CLEAN GROUND IN CORRAL,REPAIR OR REPLACE LIDS ON DUMPSTER,KEEP LIDS CLOSED & TIGHT FITTING.(SERIOUS 7-38-020)CITATION ISSUED.

    • GeneralSerious (pre-2018 form)

      Adequate number, convenient, accessible, properly designed and installed

      Inspector’s note: Inspector Comments: Inspector Comments: When toilet and lavatory facilities are provided for the patrons of food establishments, such facilities shall be adequate in number, convenient, accessible, properly designed, and installed according to the municipal code.OBSERVED NO HOT RUNNING WATER AT HAND SINKS IN KITCHEN STAFF TOILET ROOM,1ST & 2ND FLOOR BOY'S & GIRL'S,1ST & 2ND FL. STAFF,PRE-K 101 & 103 HAND SINKS & 1- COMP SINKS.MUST REPAIR OR REPLACE & PROVIDE HOT RUNNING WATER AT HAND SINKS & MAINTAIN.(SERIOUS 7-38-030)CITATION ISSUED.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Inspector Comments: Inspector Comments: All food and non-food contact surfaces of equipment and all food storage utensils shall be thoroughly cleaned and sanitized daily.MUST CLEAN ALL SHELVING UNITS & CUBBIES IN PRE-K 101 & 103,2ND FL. BOOK ROOM SHELVING UNITS.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Inspector Comments: Inspector Comments: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair.MUST REPAIR OR REPLACE DAMAGED & MISSING FLOOR TILES IN KITCHEN AT REAR DOOR,OPENING IN FLOOR ALONG WALL BASE IN ROOM 117.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Inspector Comments: Inspector Comments: The walls and ceilings shall be in good repair and easily cleaned.MUST SCRAPE & PAINT PEELING PAINT ON CEILING IN KITCHEN,WALL IN KITCHEN STAFF TOILET ROOM.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Inspector Comments: Inspector Comments: The flow of air discharged from kitchen fans shall always be through a duct to a point above the roofline.MUST REPAIR OR REPLACE 2ND FL. STAFF,PRE-K 103, LOW WATER PRESSURE.

    • GeneralMinor (pre-2018 form)

      Refrigeration and metal stem thermometers provided and conspicuous

      Inspector’s note: Inspector Comments: Inspector Comments: All food establishments that display, prepare, or store potentially hazardous foods shall have calibrated metal stem thermometers, provided and conspicuous, for refrigerated and hot food units.PRE-K 103 NEEDS THERMOMETER.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors.MUST ELEVATE & ORGANIZE ARTICLES OFF OF FLOOR & AWAY FROM WALLS IN PAPER STORAGE AREA,ROOM 117.

  28. Fail

    Canvass Re-Inspection · Fail

    2 critical8 general Show violations
    • CriticalCritical (pre-2018 form)

      No evidence of rodent or insect infestation, no birds, turtles or other animals

      Inspector’s note: All necessary control measures shall be used to effectively minimize or eliminate the presence of rodents, roaches, and other vermin/insect infestations.VIOLATION NOT CORRECTED SEE VIOLATION #14.

    • CriticalCritical (pre-2018 form)

      Previous serious violation corrected, 7-42-090

      Inspector’s note: A separate and distinct offense shall be deemed to have been committed for each Serious violation that is not corrected upon re-inspection by the health authority.PREVIOUS CRITICAL VIOLATION FROM REPORT #547681 9/19/11 VIOLATION #13 NOT CORRECTED STILL FINDING EVIDENCE OF RODENT DROPPINGS SCATTERED ON FLOOR & SHELVING UNITS IN BETWEEN CLUTTER IN CUSTODIAL ROOM 117 & PRE-K 103 ON SHELVING UNITS AT TOYS & UNDER 1- COMP SINK & CURTAIN CLOSET.MUST REMOVE DROPPINGS,CLEAN & SANITIZE AREAS.(CRITICAL 7-42-090 ) CITATION ISSUED.

    • GeneralSerious (pre-2018 form)

      Outside garbage waste grease and storage area; clean, rodent proof, all containers covered

      Inspector’s note: Inspector Comments: The area outside of the establishment used for the storage of garbage shall be clean at all times and shall not constitute a nuisance.OBSERVED OUTSIDE GARBAGE AREA NOT MAINTAINED GARBAGE CANS OVER FLOWING,LIDS WIDE OPEN,TRASH & DEBRI ON GROUND IN CORRAL,LIDS PUSHED DOWN INSIDE OF DUMPSTER.MUST CLEAN GROUND IN CORRAL,REPAIR OR REPLACE LIDS ON DUMPSTER,KEEP LIDS CLOSED & TIGHT FITTING.(SERIOUS 7-38-020)CITATION ISSUED.

    • GeneralSerious (pre-2018 form)

      Adequate number, convenient, accessible, properly designed and installed

      Inspector’s note: Inspector Comments: When toilet and lavatory facilities are provided for the patrons of food establishments, such facilities shall be adequate in number, convenient, accessible, properly designed, and installed according to the municipal code.OBSERVED NO HOT RUNNING WATER AT HAND SINKS IN KITCHEN STAFF TOILET ROOM,1ST & 2ND FLOOR BOY'S & GIRL'S,1ST & 2ND FL. STAFF,PRE-K 101 & 103 HAND SINKS & 1- COMP SINKS.MUST REPAIR OR REPLACE & PROVIDE HOT RUNNING WATER AT HAND SINKS & MAINTAIN.(SERIOUS 7-38-030)CITATION ISSUED.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: Inspector Comments: All food and non-food contact surfaces of equipment and all food storage utensils shall be thoroughly cleaned and sanitized daily.MUST CLEAN ALL SHELVING UNITS & CUBBIES IN PRE-K 101 & 103,2ND FL. BOOK ROOM SHELVING UNITS.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: Inspector Comments: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair.MUST REPAIR OR REPLACE DAMAGED & MISSING FLOOR TILES IN KITCHEN AT REAR DOOR,OPENING IN FLOOR ALONG WALL BASE IN ROOM 117.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: Inspector Comments: The walls and ceilings shall be in good repair and easily cleaned.MUST SCRAPE & PAINT PEELING PAINT ON CEILING IN KITCHEN,WALL IN KITCHEN STAFF TOILET ROOM.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Inspector Comments: The flow of air discharged from kitchen fans shall always be through a duct to a point above the roofline.MUST REPAIR OR REPLACE 2ND FL. STAFF,PRE-K 103, LOW WATER PRESSURE.

    • GeneralMinor (pre-2018 form)

      Refrigeration and metal stem thermometers provided and conspicuous

      Inspector’s note: Inspector Comments: All food establishments that display, prepare, or store potentially hazardous foods shall have calibrated metal stem thermometers, provided and conspicuous, for refrigerated and hot food units.PRE-K 103 NEEDS THERMOMETER.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Inspector Comments: All parts of the food establishment and all parts of the property used in connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors.MUST ELEVATE & ORGANIZE ARTICLES OFF OF FLOOR & AWAY FROM WALLS IN PAPER STORAGE AREA,ROOM 117.

  29. Fail

    Canvass · Fail

    3 critical8 general Show violations
    • CriticalCritical (pre-2018 form)

      Facilities to maintain proper temperature

      Inspector’s note: All food establishments that display, prepare, or store potentially hazardous food shall have adequate refrigerated food storage facilities.OBSERVED IMPROPER TEMPERATURE OF 2- DOOR REACH IN COOLER AT 56.1F & WALK IN COOLER AT 60.0F WITH POTENTIALLY HAZARDOUS FOODS STORED INSIDE.TECHNICIAN ON SITE AT THIS TIME REPAIRING COOLERS.A HELD FOR INSPECTION TAG PLACED ON UNITS.ONCE REPAIRED FAX LETTER TO (312)746-4240 WHEN READY.(CRITICAL 7-38-005A)CITATION ISSUED.

    • CriticalCritical (pre-2018 form)

      Potentially hazardous food meets temperature requirement during storage, preparation display and service

      Inspector’s note: All cold food shall be stored at a temperature of 40F or less.OBSERVED IMPROPER TEMPERATURE OF READY TO EAT TURKEY HAM ROLL AT 46.6F & 59-4OZ.CONTAINERS OF PUDDING 51.6F-56.6F STORED INSIDE OF 2- DOOR REACH IN COOLER.PRODUCT WAS VOLUNTARILY DUMPED & DENATURED.TIME & TEMPERATURE LOGS POSTED ON COOLERS AT THIS TIME.APPX.3LBS.$5.(CRITICAL 7-38-005A)CITATION ISSUED.

    • CriticalCritical (pre-2018 form)

      No evidence of rodent or insect infestation, no birds, turtles or other animals

      Inspector’s note: All necessary control measures shall be used to effectively minimize or eliminate the presence of rodents, roaches, and other vermin/insect infestations.OBSERVED EVIDENCE OF RODENT DROPPINGS INFESTATION THROUGHOUT PREMISES MORE THAN 200 IN KITCHEN BEHIND WALK IN COOLER,UNDER & NEAR HAND SINK,ON WALL OUTLET,BEHIND STOVE,ON TOP OF SAFE IN DRY FOOD STORAGE,ON TOP OF FOOD STORAGE CONTAINERS,PANS ON SHELVING UNITS,OFFICE,PAPER STORAGE ROOM ON DESK,BOXES,UNUSED AFTER SCHOOL ROOM ADJACENT TO LUNCH ROOM IN 1- COMP SINK & ON FLOOR IN CLOSET,CUSTODIAL ROOM 117 ON FLOOR IN BETWEEN CLUTTER & SHELVING UNITS,PRE- K 103 ON SHELVING UNITS,PRE- K 101 LOWER CABINETS.ALSO DEAD MOUSE AT MOTOR OF 2- DOOR REACH IN COOLER,HOLES IN FLOOR IN PAPER STORAGE NEAR RADIATOR.NO PEST CONTROL LOG BOOK ON SITE TO VIEW.BOILER ROOM DOOR WIDE OPEN.MUST REMOVE DROPPINGS,DEAD MOUSE,CLEAN & SANITIZE AREAS.SEAL HOLES IN FLOOR.P

    • GeneralSerious (pre-2018 form)

      Outside garbage waste grease and storage area; clean, rodent proof, all containers covered

      Inspector’s note: The area outside of the establishment used for the storage of garbage shall be clean at all times and shall not constitute a nuisance.OBSERVED OUTSIDE GARBAGE AREA NOT MAINTAINED GARBAGE CANS OVER FLOWING,LIDS WIDE OPEN,TRASH & DEBRI ON GROUND IN CORRAL,LIDS PUSHED DOWN INSIDE OF DUMPSTER.MUST CLEAN GROUND IN CORRAL,REPAIR OR REPLACE LIDS ON DUMPSTER,KEEP LIDS CLOSED & TIGHT FITTING.(SERIOUS 7-38-020)CITATION ISSUED.

    • GeneralSerious (pre-2018 form)

      Adequate number, convenient, accessible, properly designed and installed

      Inspector’s note: When toilet and lavatory facilities are provided for the patrons of food establishments, such facilities shall be adequate in number, convenient, accessible, properly designed, and installed according to the municipal code.OBSERVED NO HOT RUNNING WATER AT HAND SINKS IN KITCHEN STAFF TOILET ROOM,1ST & 2ND FLOOR BOY'S & GIRL'S,1ST & 2ND FL. STAFF,PRE-K 101 & 103 HAND SINKS & 1- COMP SINKS.MUST REPAIR OR REPLACE & PROVIDE HOT RUNNING WATER AT HAND SINKS & MAINTAIN.(SERIOUS 7-38-030)CITATION ISSUED.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: All food and non-food contact surfaces of equipment and all food storage utensils shall be thoroughly cleaned and sanitized daily.MUST CLEAN ALL SHELVING UNITS & CUBBIES IN PRE-K 101 & 103,2ND FL. BOOK ROOM SHELVING UNITS.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair.MUST REPAIR OR REPLACE DAMAGED & MISSING FLOOR TILES IN KITCHEN AT REAR DOOR,OPENING IN FLOOR ALONG WALL BASE IN ROOM 117.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: The walls and ceilings shall be in good repair and easily cleaned.MUST SCRAPE & PAINT PEELING PAINT ON CEILING IN KITCHEN,WALL IN KITCHEN STAFF TOILET ROOM.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: The flow of air discharged from kitchen fans shall always be through a duct to a point above the roofline.MUST REPAIR OR REPLACE 2ND FL. STAFF,PRE-K 103, LOW WATER PRESSURE.

    • GeneralMinor (pre-2018 form)

      Refrigeration and metal stem thermometers provided and conspicuous

      Inspector’s note: All food establishments that display, prepare, or store potentially hazardous foods shall have calibrated metal stem thermometers, provided and conspicuous, for refrigerated and hot food units.PRE-K 103 NEEDS THERMOMETER.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: All parts of the food establishment and all parts of the property used in connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors.MUST ELEVATE & ORGANIZE ARTICLES OFF OF FLOOR & AWAY FROM WALLS IN PAPER STORAGE AREA,ROOM 117.

  30. Pass

    Canvass · Pass

    8 general Show violations
    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: All food and non-food contact equipment and utensils shall be smooth, easily cleanable, and durable, and shall be in good repair.MUST REMOVE RUST FROM RADIATOR COVERS IN PRE-K 101 &103,WALK IN COOLER SHELVING UNITS & DRY FOOD STORAGE.MUST REPAIR OR REPLACE LOOSE HANDLE ON CABINET IN PRE-K 101,LOOSE WALL OUT LET BEHIND REACH IN FREEZER,DAMAGED SNEEZE GUARDS AT HOT HOLDING UNIT ON SERVING LINE.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: All food and non-food contact surfaces of equipment and all food storage utensils shall be thoroughly cleaned and sanitized daily.MUST CLEAN SINK,REFRIGERATOR,COUNTER TOPS IN STAFF LOUNGE,MDF ROOM SHELVING UNITS.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair.MUST CLEAN FLOORS ALONG WALL BASES IN BOILER ROOM,PREP AREA,MDF ROOM,SUPPLY ROOM.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: The walls and ceilings shall be in good repair and easily cleaned.MUST SCRAPE & PAINT PEELING PAINT ON CEILING IN PREP AREA.MUST REPLACE STAINED CEILING TILES IN PRE-K 103,LUNCH ROOM,MISSING WALL BASES IN LUNCH ROOMS.

    • GeneralMinor (pre-2018 form)

      Lighting: required minimum foot-candles of light provided, fixtures shielded

      Inspector’s note: All rooms in which food or drink is prepared, or in which utensils are washed, shall be lighted so that a minimum of 50-foot candles of light is available on all work surfaces.REPLACE BURNT OUT LIGHT BULB IN 2ND FL. MOP SINK CLOSET & 3RD FL. GIRL'S.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health.MUST REPAIR OR REPLACE 2ND FL. BOY'S HAND SINK IN POOR REPAIR & LOW WATER PRESSURE,3RD FL. WOMEN'S HAND SINK FAUCET ADJUSTED,PRE-K 101 LOW WATER PRESSURE AT HAND SINK IN TOIET ROOM.

    • GeneralMinor (pre-2018 form)

      Refrigeration and metal stem thermometers provided and conspicuous

      Inspector’s note: All food establishments that display, prepare, or store potentially hazardous foods shall have calibrated metal stem thermometers, provided and conspicuous, for refrigerated and hot food units.PRE-K 101.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: All parts of the food establishment and all parts of the property used in connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors.MUST REMOVE,ELEVATE ARTICLES OFF OF FLOOR & AWAY FROM WALLS IN BOILER ROOM,MDF ROOM,SUPPLY ROOM.

  31. Pass

    Canvass · Pass

    5 general Show violations
    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: All utensils shall be thoroughly cleaned and sanitized after each usage. MUST CLEAN-SANITIZE; CAN OPENER IN KITCHEN AND MOP SINKS INSIDE 2ND AND 3RD FLOOR CLOSETS.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair. MUST CLEAN FLOORS THRU-OUT STORAGE ROOMS AND MOP CLOSETS.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: The walls and ceilings shall be in good repair and easily cleaned. MUST CLEAN FANS INSIDE BOTH PRE-K CLASSROOMS.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. MUST REPAIR FAUCETS INSIDE 3RD FLOOR BOY'S WASHROOM, STAFF, MEN'S 1ST FLOOR WASHROOM AND WOMEN 3RD FLOOR WASHROOM.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Must remove clutter inside storage rooms and mop closets, clean and organize to prevent pest harborage. Articles must be stored off floor, away from walls.

  32. Pass

    Canvass · Pass

    6 general Show violations
    • GeneralMinor (pre-2018 form)

      Food and non-food contact surfaces properly designed, constructed and maintained

      Inspector’s note: All food and non-food contact equipment and utensils shall be smooth, easily cleanable, and durable, and shall be in good repair. MUST REPAIR CABINETS DOORS IN PRE-K CLASSROOM #101.

    • GeneralMinor (pre-2018 form)

      Food and non-food contact equipment utensils clean, free of abrasive detergents

      Inspector’s note: All utensils shall be thoroughly cleaned and sanitized after each usage. MUST CLEAN-SANITIZE; PRE-K CLASSROOM 101 CABINETS, AND WASHROOMS HAND BOWLS IN 2ND BOYS AND GIRLS 2ND FLOOR WASHROOMS.

    • GeneralMinor (pre-2018 form)

      Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used

      Inspector’s note: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair. MUST SEAL WALK-IN-COOLER RUSTY FLOOR, AND CLEAN FLOORS THRU-OUT, STORAGE CLOSETS, WASHROOMS, PRE-K CLASSROOMS, LUCHROOMS AND BOILER ROOM.

    • GeneralMinor (pre-2018 form)

      Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods

      Inspector’s note: The walls and ceilings shall be in good repair and easily cleaned. MUST CLEAN VENT COVERS THRU-OUT WASHROOMS, REPLACE DAMAGED CEILING PANELS INSIDE STAFF/MENS 2ND FLOOR WASHROOM AND REMOVE PEELING PAINT FROM CEILING THRU-OUT KITCHEN.

    • GeneralMinor (pre-2018 form)

      Ventilation: rooms and equipment vented as required: plumbing: installed and maintained

      Inspector’s note: Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. MUST REPAIR FAUCETS ON HAND WASHING BOWLS IN WASHROOMS THRU-OUT PREMISES AND REPAIR DISH MACHINE IN KITCHEN.

    • GeneralMinor (pre-2018 form)

      Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored

      Inspector’s note: Must remove unnecessary articles thru-out boiler room, pre-k classrooms and closets, clean and organize to prevent pest harborage.

More in ZIP 60623