Kidtropolis Childcare Developmental Center LLC
8102-8104 S Halsted ST FL 1st, Chicago, IL 60620
Daycare Above and Under 2 Years ZIP 60620 Risk 1 (High)
Passed · as of May 20, 2026
Kidtropolis Childcare Developmental Center LLC was last inspected on May 20, 2026 with a result of “Pass”. Inspectors found 2 violations.
Latest inspection
May 20, 2026 · License
Result: Pass
2 general-
GeneralFacility upkeep
Equipment or surfaces were in poor repair or made of material that can’t be cleaned.
Inspector’s note: Observed the oven door in poor repair (missing). Must repair and maintain.
Official wording (code 47)
Food & non-food contact surfaces cleanable, properly designed, constructed & used
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Noted the ceiling tiles in poor repair (missing and/or damaged). Must repair and maintain
Official wording (code 55)
Physical facilities installed, maintained & clean
Inspection history
18 inspections on record
-
Pass
Canvass · Pass
2 general Show violations
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Observed missing and water damaged ceiling tile in the infant classroom and water stained ceiling tile in pre-school classroom; intructed to replace missing and damaged ceiling tile where needed.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Instructed to clean the floor in the kitchen under storage shelf.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Pass
License Re-Inspection · Pass
1 critical2 general Show violations
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: 5-202.12 (b-d) : must repair or replace leaky pipe at hand sink in staff toilet room.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: 6-201.13 : must repair or replace stained ceiling tiles in caterpillars room .
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: 6-201.16 : must scrape chipping paint in cool kids- walls , window sills & toilet room.caterpillars room-walls.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Fail
License · Fail
1 critical4 general Show violations
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: Must repair or replace leaky pipe at hand sink in staff toilet room.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
GeneralPests
Insects, rodents, or animals were present, or the building wasn’t sealed against them.
Inspector’s note: Observed evidence of appx. 75 or more mice droppings in kitchen- on floorunder dry food storage shelf,under hand sink,next to dish storage cart,next to stove,inside lower drawer of stove.cool kids room-on cart with disposable paper goods.caterpillars room-on toy shelves, lower shelf of changing table,on floor next to baby bed against the wall.mopsink closet-on floor next to mop sink.kids & staff toilet room-on floor next to toilet and under hand sink.must remove droppings clean and sanitize areas. Recommended to have a pest control operator to service premises on or after 9/19/24.(priority foundation 7-38-020(a)(citation issued)
Official wording (code 38)
Insects, rodents, & animals not present
-
GeneralPests
Insects, rodents, or animals were present, or the building wasn’t sealed against them.
Inspector’s note: Observed a gap along bottom of cool kids front door must make door tight fitting to prevent rodent entry.
Official wording (code 38)
Insects, rodents, & animals not present
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Must repair or replace hole in wall behind door in cool kids toilet room & staff toilet room,wall in poor repair in mopsink closet,stained ceiling tiles in caterpillars room & cool kids room.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Must scrape chipping paint in cool kids- walls , window sills & toilet room.caterpillars room-walls.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Pass
License Re-Inspection · Pass
7 general Show violations
-
GeneralFood handling
Clean utensils, equipment, or linens weren’t stored and handled properly.
Inspector’s note: 4-903.11 (a;b;d) : must invert multi-use utensils on shelving units in kitchen.
Official wording (code 44)
Utensils, equipment & linens: properly stored, dried, & handled
-
GeneralFacility upkeep
Equipment or surfaces were in poor repair or made of material that can’t be cleaned.
Inspector’s note: 4-501.11 : observed broken sink stoppers must provide sink stoppers to hold water inside of sink basin of 3- compartment sink.
Official wording (code 47)
Food & non-food contact surfaces cleanable, properly designed, constructed & used
-
GeneralFacility upkeep
Equipment and surfaces were dirty.
Inspector’s note: 4-601.11(c) : must clean dust build up from some shelving units in all classrooms.
Official wording (code 49)
Non-food/food contact surfaces clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: 6-501.13 : must clean debris build up from floor along wall bases in kitchen
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: 6-501.114 : must elevate articles off of floor under 3- compartment sink and food shelves.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: 6-201.16 : must scrape and paint chipping paint on pre-school window sills and walls,toddlers-window sills,infants-class room & toilet room
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: 6-201.13 : must repair or replace stained ceiling tiles in pre-school and infants room,missing and damaged wall base near refrigerator and wall near rear door in,door trim in kids toilet room in infants room
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Fail
License Re-Inspection · Fail
2 critical7 general Show violations
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: 5-202.12 (a) :still observed hot running water temperature at hand sink in staff toilet room at 89.2f.must have hot running water at 100.0f must repair and maintain.(priority 7-38-030(c)(citation issued)
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: 5-202.12 (b-d) : observed low hot and cold water pressure at hand sink in staff toilet room must repair and maintain.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
GeneralFood handling
Clean utensils, equipment, or linens weren’t stored and handled properly.
Inspector’s note: 4-903.11 (a;b;d) : must invert multi-use utensils on shelving units in kitchen
Official wording (code 44)
Utensils, equipment & linens: properly stored, dried, & handled
-
GeneralFacility upkeep
Equipment or surfaces were in poor repair or made of material that can’t be cleaned.
Inspector’s note: 4-501.11 : observed broken sink stoppers must provide sink stoppers to hold water inside of sink basin of 3- compartment sink.
Official wording (code 47)
Food & non-food contact surfaces cleanable, properly designed, constructed & used
-
GeneralFacility upkeep
Equipment and surfaces were dirty.
Inspector’s note: 4-601.11(c) : must clean dust build up from some shelving units in all classrooms.
Official wording (code 49)
Non-food/food contact surfaces clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: 6-201.13 : must repair or replace stained ceiling tiles in pre-school and infants room,missing and damaged wall base near refrigerator and wall near rear door in,door trim in kids toilet room in infants room.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: 6-501.114 : must elevate articles off of floor under 3- compartment sink and food shelves.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: 6-501.13 : must clean debris build up from floor along wall bases in kitchen.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: 6-201.16 : must scrape and paint chipping paint on pre-school window sills and walls,toddlers-window sills,infants-class room & toilet room
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Fail
License · Fail
3 critical8 general Show violations
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: Observed hot running water temperature at hand sink in staff toilet room at 89.2f.must have hot running water at 100.0f must repair and maintain.(priority 7-38-030(c)(citation issued)
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: Observed low hot and cold water pressure at hand sink in staff toilet room must repair and maintain.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
CriticalFood temperature
Cold food was held above a safe temperature.
Inspector’s note: Observed improper temperatures of tcs foods such as 8.5 gallons of milk ranging from 46.4f-47.2f inside of refrigerator. Product was discarded by manager must have cold holding foods at 41.0f or below.appx.8.5 gallons $26.35.(priority 7-38-005)(cos)(citation issued)
Official wording (code 22)
Proper cold holding temperatures
-
GeneralFood temperature
Not enough equipment, or the wrong method, to cool and hold food at safe temperatures.
Inspector’s note: Observed improper temperature of refrigerator in kitchen at 48.9f with tcs foods stored inside.must have cold holding unit at 41.0f or below.the manager adjusted the temperature gauge, and the internal air temperature is now 42.8f. (cos)(priority 7-38-005)(citation issued)
Official wording (code 33)
Proper cooling methods used; adequate equipment for temperature control
-
GeneralFood handling
Clean utensils, equipment, or linens weren’t stored and handled properly.
Inspector’s note: Must invert multi-use utensils on shelving units in kitchen.
Official wording (code 44)
Utensils, equipment & linens: properly stored, dried, & handled
-
GeneralFacility upkeep
Equipment or surfaces were in poor repair or made of material that can’t be cleaned.
Inspector’s note: Observed broken sink stoppers must provide sink stoppers to hold water inside of sink basin of 3- compartment sink.
Official wording (code 47)
Food & non-food contact surfaces cleanable, properly designed, constructed & used
-
GeneralFacility upkeep
Equipment and surfaces were dirty.
Inspector’s note: Must clean dust build up from some shelving units in all classrooms.
Official wording (code 49)
Non-food/food contact surfaces clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Must scrape and paint chipping paint on pre-school window sills and walls,toddlers-window sills,infants-class room & toilet room.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Must elevate articles off of floor under 3- compartment sink and food shelves.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Must clean debris build up from floor along wall bases in kitchen.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Must repair or replace stained ceiling tiles in pre-school and infants room,missing and damaged wall base near refrigerator and wall near rear door in,door trim in kids toilet room in infants room.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Pass
Canvass · Pass
3 general Show violations
-
GeneralFacility upkeep
Plumbing problems, or missing protection against backflow.
Inspector’s note: Observed the hand sink hot and cold water pressure in the staff washroom in the infant room is low. Must repair/replace and maintain.
Official wording (code 51)
Plumbing installed; proper backflow devices
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Observed peeling paint in the infant class room remove and water damaged ceiling tiles also in the infants room. Must repair,repaint and/or replace as needed.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Floors need cleaning along the wall base and in the corners in the kitchen to remove spills and debris.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Conditional
Canvass · Pass w/ Conditions
1 critical8 general1 paperwork Show violations
-
CriticalManagement & training
No one in charge was present who knew the food-safety rules.
Inspector’s note: Pic doesn't have a food managers certificate.must provide and maintain.(priority foundation 7-38-012)
Official wording (code 1)
Person in charge present, demonstrates knowledge, and performs duties
-
GeneralFood temperature
Thermometers were missing or inaccurate.
Inspector’s note: Observed no thermometer in kitchen refrigerator.must provide and maintain.
Official wording (code 36)
Thermometers provided & accurate
-
GeneralPests
Insects, rodents, or animals were present, or the building wasn’t sealed against them.
Inspector’s note: Observed an appx. "1/2-3/4" gap along bottom of front south door and rear west door in infants room .must make doors tight fitting.
Official wording (code 38)
Insects, rodents, & animals not present
-
GeneralFood handling
Clean utensils, equipment, or linens weren’t stored and handled properly.
Inspector’s note: Must invert multi-use utensils on dish storage shelves.
Official wording (code 44)
Utensils, equipment & linens: properly stored, dried, & handled
-
GeneralFacility upkeep
Equipment and surfaces were dirty.
Inspector’s note: Must clean dust build up from shelving units in all class rooms.
Official wording (code 49)
Non-food/food contact surfaces clean
-
GeneralFacility upkeep
Plumbing problems, or missing protection against backflow.
Inspector’s note: Must repair or replace low cold and hot water pressure at hand sink in staff toilet room.
Official wording (code 51)
Plumbing installed; proper backflow devices
-
GeneralFacility upkeep
Toilet rooms weren’t built, stocked, or cleaned properly.
Inspector’s note: Observed no garbage can with lid in staff toilet room .must provide and maintain.
Official wording (code 53)
Toilet facilities: properly constructed, supplied, & cleaned
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Must finish wall to be smooth and easily cleanable in infants toilet room.must repair or replace stained ceiling tiles in infants and hallway outside of office,missing wall bases outside of office,damaged wall in mop sink.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Must scrape and paint peeling paint on walls in kitchen behind door,outside of office,toddlers and window sills in infants class rooms.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
PaperworkManagement & training
No manager on duty held a City of Chicago food sanitation certificate.
Inspector’s note: Observed no certified food managers certificate posted to view while tcs foods are being prepared,handled and served such as (milk).must provide and maintain.(priority foundation 7-38-012)(citation issued)
Official wording (code 2)
City of chicago food service sanitation certificate
-
-
Pass
License · Pass
2 general Show violations
-
GeneralFacility upkeep
Plumbing problems, or missing protection against backflow.
Inspector’s note: Observed leaking hot water faucet and leak under hand washing sink in washroom near kitchen. Instructed manager to repair and maintain.
Official wording (code 51)
Plumbing installed; proper backflow devices
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Observed openings around pipe fittings under hand washing sink in north washroom in infant room, openings along lower wall near utility sink in closet, peeling paint on walls in classrooms. Instructed manager to repair and maintain.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Pass
License Re-Inspection · Pass
1 general Show violations
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Violation Codes: 6-201.16 Inspector Comments: MUST SCRAPE AND PAINT PEELING PAINT ON WALLS IN ALL CLASS ROOMS.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Fail
License · Fail
1 critical8 general Show violations
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: Observed handwashing sinks water temperature in adult toilet room at 77.0f and kids front toilet room at 86.4f. Must have a minimum of 100.0f for hand washing.must provide hot running water and maintain. (priority 7-38-030(c)(citation issued)
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
GeneralFood handling
Clean utensils, equipment, or linens weren’t stored and handled properly.
Inspector’s note: Must invert multi-use utensils on dish storage shelf.
Official wording (code 44)
Utensils, equipment & linens: properly stored, dried, & handled
-
GeneralFacility upkeep
Equipment or surfaces were in poor repair or made of material that can’t be cleaned.
Inspector’s note: Must provide sink stoppers for 3- compartment sink.
Official wording (code 47)
Food & non-food contact surfaces cleanable, properly designed, constructed & used
-
GeneralFacility upkeep
Dishwashing equipment wasn’t set up, maintained, or used correctly.
Inspector’s note: Observed faucet not long enough at 3- compartment sink to reach far left and right compartments of sink to fill them up with water to wash and sanitize multi-use utensils.must provide faucet handle long enough to reach all compartments. (priority foundation 7-38-025)(citation issued)
Official wording (code 48)
Warewashing facilities: installed, maintained & used; test strips
-
GeneralFacility upkeep
Equipment and surfaces were dirty.
Inspector’s note: Must clean dust build up at lower shelf of changing table in busy bee room.
Official wording (code 49)
Non-food/food contact surfaces clean
-
GeneralFacility upkeep
Toilet rooms weren’t built, stocked, or cleaned properly.
Inspector’s note: Must provide a lid on garbage can in staff toilet room.
Official wording (code 53)
Toilet facilities: properly constructed, supplied, & cleaned
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Must replace or repair stained ceiling tiles in pre-school room and busy bee room, lower wall damaged in mop sink closet. Must seal hole in wall in kids front toilet room, seal gap at wall outlet in pre-school room.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Must clean debris build up from walls in kitchen, busy bee room.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Must scrape and paint peeling paint on walls in all class rooms.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Conditional
Canvass · Pass w/ Conditions
1 critical3 general Show violations
-
CriticalManagement & training
No written plan or kit for cleaning up vomit or diarrhea.
Inspector’s note: Found no clean up kit for responding to vomiting and diarrheal events on site. Instructed to provide a clean up kit and maintain. Priority foundation violation 7-38-005 no citation issued
Official wording (code 5)
Procedures for responding to vomiting and diarrheal events
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Floors in the corners and under/around heavy equipment with dirt, dead insects and debris. Floor tiles throughout stained/grungy. Instructed to detail clean and maintain floors.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Ceiling tiles with water stains and/or missing. Instructed to replace/provide ceiling tiles.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Ventilation or lighting was inadequate.
Inspector’s note: Poor lighting due to blown bulbs in infant classroom and food preparation area. Instructed to proide adequate lighting and maintain.
Official wording (code 56)
Adequate ventilation & lighting; designated areas used
-
-
Conditional
Canvass · Pass w/ Conditions
3 critical2 general Show violations
-
CriticalManagement & training
Staff weren’t trained on, or didn’t follow, the rules for reporting illness.
Inspector’s note: Observed no employee health policy on site. Instructed to provide an employee health policy that includes a signed acknowledgement from each employee. Priority foundation. No citation issued.
Official wording (code 3)
Management, food employee and conditional employee; knowledge, responsibilities and reporting
-
CriticalManagement & training
No written plan or kit for cleaning up vomit or diarrhea.
Inspector’s note: Observed no written procedure for responding to vomit or diarrhea events that can potentially occur inside of the food establishment. Priority foundation. No citation issued.
Official wording (code 5)
Procedures for responding to vomiting and diarrheal events
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: Observed no handwashing sign located at the hand washing sink in the food prep area. Instructed to provide.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
GeneralFood temperature
Thermometers were missing or inaccurate.
Inspector’s note: Observed no thermometer inside of the refrigerator in the infants room. Instructed to provide.
Official wording (code 36)
Thermometers provided & accurate
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Observed floors in the infant room with accumulated dust debris. Instructed to clean.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Pass
Canvass · Pass
2 general Show violations
-
GeneralMinor (pre-2018 form)
Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored
Inspector’s note: Observed unnecessary articles/ clutter inside one rest room in infant room. Instructed to organize and remove unnecessary articles.
-
GeneralMinor (pre-2018 form)
Food handler requirements met
Inspector’s note: Observed two employees are not certified food handler. Instructed all employees to provide food handler certificates.
-
-
Pass
Canvass · Pass
2 general Show violations
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Observed the 3 compartment sink faucet base leaking. Instructed to repair and maintain all plumbing.
-
GeneralMinor (pre-2018 form)
Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored
Inspector’s note: Observed a wet mop stored inside of the mop bucket. Instructed to store wet mops hanging or inverted.
-
-
Pass
License Re-Inspection · Pass
1 general Show violations
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Floor needs detailed cleaning in corners and along wallbase in infant room. Instd to clean same.
-
-
Fail
License · Fail
2 general Show violations
-
GeneralSerious (pre-2018 form)
Adequate number, convenient, accessible, properly designed and installed
Inspector’s note: Handsink in childrens toilet room in poor repair, no hot running water nor tempered water under city pressure. Instd to provide same. Citation issued 7-38-030 serious.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Floor needs detailed cleaning in corners and along wallbase in infant room. Instd to clean same.
-