Holy Angels School was last inspected on May 1, 2026 with a result of “Pass”. Inspectors found no violations.
Latest inspection
May 1, 2026 · Canvass
Result: Pass
No violationsNo violations were recorded at this inspection.
Inspection history
21 inspections on record
-
Pass
Canvass · Pass
2 general Show violations
-
GeneralFacility upkeep
Plumbing problems, or missing protection against backflow.
Inspector’s note: Observed the one of the hand sinks in the girls washroom (1st floor) not working. Must repair and mainatain.
Official wording (code 51)
Plumbing installed; proper backflow devices
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Observed openings along the wall base floor in the pre-k room 112. Must seal all openings to prevent entry points for pests.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Pass
Canvass · Pass
2 general Show violations
-
GeneralFacility upkeep
Equipment and surfaces were dirty.
Inspector’s note: Must clean the interior of the 2 door reach in cooler to remove debris at the bottom.
Official wording (code 49)
Non-food/food contact surfaces clean
-
GeneralFacility upkeep
Toilet rooms weren’t built, stocked, or cleaned properly.
Inspector’s note: Must provide and maintain a small garbage can with a lid in the teachers and girls washrooms.
Official wording (code 53)
Toilet facilities: properly constructed, supplied, & cleaned
-
-
Pass
Canvass · Pass
No violations
-
Pass
Canvass · Pass
2 general Show violations
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Observed large hole around gas line in wall of kitchen. Must seal space around pipe to prevent pest entry. Observed holes along the bottom of walls in the kitchen area. Must fill holes or provide coving to prevent pest entry. Must maintain same.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: I observed peeling paint on the stone walls of the kitchen. Must remove all peeling paint to make it smooth, even, and easily cleanable. Must maintain same.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Pass
Canvass · Pass
No violations
-
Pass
Canvass · Pass
2 general Show violations
-
GeneralPests
Insects, rodents, or animals were present, or the building wasn’t sealed against them.
Inspector’s note: The exit at door #3 is not rodent/insect proofed. Instructed to seal the 1/2" gap at that door. Maintain same.
Official wording (code 38)
Insects, rodents, & animals not present
-
GeneralFacility upkeep
Plumbing problems, or missing protection against backflow.
Inspector’s note: Found the left washbowl in the girls toilet room (by room 105) with extremely low hot/cold water pressure. Instructed to fix and maintain.
Official wording (code 51)
Plumbing installed; proper backflow devices
-
-
Conditional
Canvass · Pass w/ Conditions
2 critical Show violations
-
CriticalManagement & training
Staff weren’t trained on, or didn’t follow, the rules for reporting illness.
Inspector’s note: No employee health policy on premises as required; must provide. Instructed to provide documentation of employees responsibility to report any illness transmissible through food. Priority foundation violation 7-38-010.
Official wording (code 3)
Management, food employee and conditional employee; knowledge, responsibilities and reporting
-
CriticalManagement & training
No written plan or kit for cleaning up vomit or diarrhea.
Inspector’s note: No vomit and diarrheal clean up procedure on premises as required; must provide. Instructed the pic that a vomit and diarrheal clean up procedure must be documented and the necessary supplies on hand in the event of a vomit and diarrheal incident on premises. Priority foundation violation 7-38-005.
Official wording (code 5)
Procedures for responding to vomiting and diarrheal events
-
-
Pass
Canvass · Pass
1 general Show violations
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Observed excessive dust and grease build up on filters inside ventilation hood in kitchen area. Advised must detail clean and sanitize. Must maintain same.
-
-
Pass
Canvass · Pass
3 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact equipment utensils clean, free of abrasive detergents
Inspector’s note: Clean exterior of milk cooler and door gaskets of milk cooler in lunchroom.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Clean floors along walls and in all corners in lunchroom.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Replace missing baseboards near stove in kitchen. Remove peeling paint and repaint door/window frame and surfaces in kitchen. Repair damaged door sweeps.
-
-
Conditional
Canvass · Pass w/ Conditions
3 general Show violations
-
GeneralSerious (pre-2018 form)
* certified food manager on site when potentially hazardous foods are prepared and served
Inspector’s note: No city of chicago food service certificate on premises as required while handling foods. Two persons on duty, one left her certicate at home and the other has a receipt from 8/29/15 from malcolm x verifying payment for a copy of her certificate. She has not received it as of this date. Instructed that a valid certificate must be on premises at all times with the managers/food handlers. Serious violation issued 7-38-012.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Must clean floors in corner areas of kitchen.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Observed peeling paint on the wall and small holes at the bottom area of the wall of the serving line/window; must remove peeling paint and seal the holes observed in the lower wall. Some peeling paint on the wall next to the stove; remove and repaint. Clean window sills in kitchen to remove debris from walls. Some dust observed on the vents above the cooking equipment; clean and remove dust.
-
-
Conditional
Canvass · Pass w/ Conditions
2 general Show violations
-
GeneralSerious (pre-2018 form)
Toilet rooms enclosed clean, provided with hand cleanser, sanitary hand drying devices and proper waste receptacles
Inspector’s note: Inadequate hands washing facilities. Found no hand soap, inoperable hand dryer at boys' toilet room. Instructed to provide at all times. Serious citation issued 7-38-030
-
GeneralMinor (pre-2018 form)
Refrigeration and metal stem thermometers provided and conspicuous
Inspector’s note: Inaccurate metal stem thermometer with kitchen mgr. Instructed to obtain an accurate one.
-
-
Pass
Canvass · Pass
4 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact equipment utensils clean, free of abrasive detergents
Inspector’s note: Clean interior bottom of cold holding unit in corner of serving area outside of kitchen.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Missing floor tile in serving area of kitchen; replace where needed.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Clean vents above stove in hooded system to remove dust in kitchen. Some peeling paint on ceiling of boys washroom (west side of building); remove and repaint.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Must repair the following plumbing violations: two urinals in boys washroom (west side), two urinals in boys washroom (east side) and one toilet in boys washroom (east side) all on second floor. One toilet in pre-k washroom.
-
-
Pass
Canvass Re-Inspection · Pass
No violations
-
Fail
Canvass · Fail
2 general Show violations
-
GeneralSerious (pre-2018 form)
No evidence of rodent or insect outer openings protected/rodent proofed, a written log shall be maintained available to the inspectors
Inspector’s note: Found 7 entry/exit doors not rodent proofed. 1/4 gap at bottom of doors. Must have all outer openings tightly sealed to prevent all rodent entry. Serious citation issued 7-38-020 citation issued outer openings not protected.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Floors in cafeteria, janitors closetand throughout basement in need of cleaning. Must remove all dead insects from floors. Must clean and maintain at all times.
-
-
Pass
Canvass Re-Inspection · Pass
2 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: Must replace missing stall door in 1st floor girls washroom on west end of building.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Must repair 1st toilet bowl in 1st floor girls washroom west end of building. Must repair toilet bowl in womens staff washroom on 1st floor.
-
-
Fail
Canvass · Fail
3 general Show violations
-
GeneralSerious (pre-2018 form)
Adequate number, convenient, accessible, properly designed and installed
Inspector’s note: Hand washing facilities not properly maintained. Noted no hot running water at washbowls in student and staff washrooms on site. Must repair and provide hot running water at all sinks. Serious citation issued 7-38-030
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: Must replace missing stall door in 1st floor girls washroom on west end of building.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Must repair 1st toilet bowl in 1st floor girls washroom west end of building. Must repair toilet bowl in womens staff washroom on 1st floor.
-
-
Pass
Canvass · Pass
4 general Show violations
-
GeneralMinor (pre-2018 form)
Clean multi-use utensils and single service articles properly stored: no reuse of single service articles
Inspector’s note: Found large pots not stored properly.(must store inverted)
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Found floors not swept at entertainment room/next to kitchen.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Found walls not clean and with some chipping paint at main lunchroom.
-
GeneralMinor (pre-2018 form)
Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored
Inspector’s note: Found pieces of old wood at boiler areas that must be disposed.
-
-
Pass
Canvass Re-Inspection · Pass
7 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: Seal small opening along bottom of door at main entrance.
-
GeneralMinor (pre-2018 form)
Food and non-food contact equipment utensils clean, free of abrasive detergents
Inspector’s note: Must detail clean hood over cooking equipment and remove dust build up. Must also detail clean walls and ceilings in prep kitchen and cafeteria and remove spider webs and food spills.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Must detail clean floors along walls,behind shelving racks and under 2 compartment sink.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Must seal large opening in wall in cafeteria.
-
GeneralMinor (pre-2018 form)
Lighting: required minimum foot-candles of light provided, fixtures shielded
Inspector’s note: Must repair broken light in 1st floor mop sink closet.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Found 1st floor mop sink completely clogged. Must repair same. Must repair all broken toilet bowls and urinals throughout washrooms where needed.
-
GeneralMinor (pre-2018 form)
Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored
Inspector’s note: Must remove unnecessary items and extreme clutter from janitors room and better organize remaining items and store all items 6 inches off floor.
-
-
Fail
Canvass · Fail
1 critical7 general Show violations
-
CriticalCritical (pre-2018 form)
Adequate number, convenient, accessible, designed, and maintained
Inspector’s note: No hot running water at washbowls in washrooms throughout premises. Must repair and provide hot running water at all sinks to allow for proper hand washing. Critical citation issue 7-38-030.
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: Seal small opening along bottom of door at main entrance.
-
GeneralMinor (pre-2018 form)
Food and non-food contact equipment utensils clean, free of abrasive detergents
Inspector’s note: Must detail clean hood over cooking equipment and remove dust build up. Must also detail clean walls and ceilings in prep kitchen and cafeteria and remove spider webs and food spills.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Must detail clean floors along walls,behind shelving racks and under 2 compartment sink.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Must seal large opening in wall in cafeteria.
-
GeneralMinor (pre-2018 form)
Lighting: required minimum foot-candles of light provided, fixtures shielded
Inspector’s note: Must repair broken light in 1st floor mop sink closet.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Found 1st floor mop sink completely clogged. Must repair same. Must repair all broken toilet bowls and urinals throughout washrooms where needed.
-
GeneralMinor (pre-2018 form)
Premises maintained free of litter, unnecessary articles, cleaning equipment properly stored
Inspector’s note: Must remove unnecessary items and extreme clutter from janitors room and better organize remaining items and store all items 6 inches off floor.
-
-
Pass
Complaint · Pass
No violations