Stephen Decatur School was last inspected on September 29, 2026 with a result of “Pass”. Inspectors found 1 violation.
Latest inspection
September 29, 2026 · Canvass Re-Inspection
Result: Pass
1 general-
GeneralFacility upkeep
Plumbing problems, or missing protection against backflow.
Inspector’s note: 5-205.15 repair the source of the water leak beneath the steam table at the service line.
Official wording (code 51)
Plumbing installed; proper backflow devices
Inspection history
21 inspections on record
-
Pass
Canvass · Pass
1 critical3 general Show violations
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: Instructed to remove soap and paper towel dispenser from the lunchroom one compartment dump sink. Instructed to use the boys and girls washroom wash bowls for hand washing purposes that are adjacent to the lunchroom entrance.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
GeneralFacility upkeep
Equipment and surfaces were dirty.
Inspector’s note: Must not use cloth towels as liner for shelving in the dish room.
Official wording (code 49)
Non-food/food contact surfaces clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Noted dirty floor drains under both one compartment prep sinks. Must clean and maintain.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Noted open 1/4 to 1/2 inch crack/crevice along the baseboard coving and floor behind the cooking equipment, in the dry food storage room and in the lunchroom office. Instructed to seal any openings along baseboards throughout.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Pass
Canvass · Pass
1 critical2 general Show violations
-
CriticalHygiene & sanitation
Hand sinks were missing, blocked, or not stocked with soap and towels.
Inspector’s note: Original building side boys and girls handwash sinks hot and cold water push buttons with less than 15 seconds running water time when pushed. Must recalibrate said handwash sinks to minimal 15 seconds running water time.
Official wording (code 10)
Adequate handwashing sinks properly supplied and accessible
-
GeneralPests
Insects, rodents, or animals were present, or the building wasn’t sealed against them.
Inspector’s note: Observed 1/4 inch gap at rear exit doors sweeps by main entrance. Must rodent proof doors and maintain.
Official wording (code 38)
Insects, rodents, & animals not present
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Observed accumulated dirt build up inside prep area floor drains. Must clean interior of floor drains and maintain.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Pass
Canvass · Pass
No violations
-
Pass
Canvass · Pass
No violations
-
Pass
Canvass · Pass
No violations
-
Pass
Canvass · Pass
2 general Show violations
-
GeneralFacility upkeep
Plumbing problems, or missing protection against backflow.
Inspector’s note: Observed small water leak at drain pipe underneath the 3-compartment sink.instructed to repair noted plumbing leak and to maintain.
Official wording (code 51)
Plumbing installed; proper backflow devices
-
GeneralFacility upkeep
Toilet rooms weren’t built, stocked, or cleaned properly.
Inspector’s note: Observed no covered waste receptacles provided in the unisex washrooms located in the (annex building).instructed to provide and maintain.
Official wording (code 53)
Toilet facilities: properly constructed, supplied, & cleaned
-
-
Conditional
Canvass · Pass w/ Conditions
1 critical3 general Show violations
-
CriticalManagement & training
No written plan or kit for cleaning up vomit or diarrhea.
Inspector’s note: Incomplete cleaning supply kit for vomiting and diarrheal events. Instructed to provide disinfectant effective for norovirus. Priority foundation 7-38-005 no citation issued.
Official wording (code 5)
Procedures for responding to vomiting and diarrheal events
-
GeneralPests
Insects, rodents, or animals were present, or the building wasn’t sealed against them.
Inspector’s note: Exit door #8 with 1/4 gap on the left side bottom of the door. Instructed to repair make the door tight fitting and rodent/insects proofed.
Official wording (code 38)
Insects, rodents, & animals not present
-
GeneralFacility upkeep
Toilet rooms weren’t built, stocked, or cleaned properly.
Inspector’s note: Waste receptacles inside the ladies staff washroom must have a lid/cover for feminine items.
Official wording (code 53)
Toilet facilities: properly constructed, supplied, & cleaned
-
GeneralFacility upkeep
Floors, walls, or ceilings were damaged or dirty.
Inspector’s note: Missing and water stained ceiling panels in the hallway. Must replace and maintain.
Official wording (code 55)
Physical facilities installed, maintained & clean
-
-
Conditional
Canvass · Pass w/ Conditions
1 critical Show violations
-
CriticalManagement & training
No written plan or kit for cleaning up vomit or diarrhea.
Inspector’s note: 2-501.11 found no vomit and diarrhea clean up policy/spill kit. Priority foundation. No citation issued.7-38-005. Must provide.
Official wording (code 5)
Procedures for responding to vomiting and diarrheal events
-
-
Pass
Canvass · Pass
2 general Show violations
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Observed main hallway with stained and missing ceiling tiles. Must replace all missing ceiling tiles and replace all stained ceiling tiles. Must maintain ceiling.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Observed 3/4 urinals in boys washroom with no running water and strong urine odor. Must supply running water to urinals to flush at all times.
-
-
Pass
Canvass · Pass
No violations
-
Pass
Canvass · Pass
1 general Show violations
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: Observed water pressure in boys nd girls bathrooms very low. Water pressure must be restored and maintained for children to wash hands.
-
-
Pass
Canvass · Pass
2 general Show violations
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Floors in rear storage area room not clean, needs detailed cleaning(corners).
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Ceiling in kitchen prep area had peeling paint, shall be repaired/sealed. Damaged/stained ceiling tiles outside classroom (kindergarten)shall be repaired/replaced.
-
-
Pass
Canvass · Pass
3 general Show violations
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Found floors not clean at boiler areas.(along walls)
-
GeneralMinor (pre-2018 form)
Lighting: required minimum foot-candles of light provided, fixtures shielded
Inspector’s note: Found burnt light bulbs inside hood exhaust unit and reach in cooler.
-
GeneralMinor (pre-2018 form)
Food (ice) dispensing utensils, wash cloths properly stored
Inspector’s note: Found wash cloths not stored properly.
-
-
Pass
Canvass Re-Inspection · Pass
1 general Show violations
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Re seal baseboard/coving on wall by the kitchen staff washroom
-
-
Fail
Canvass · Fail
2 general Show violations
-
GeneralSerious (pre-2018 form)
Adequate number, convenient, accessible, properly designed and installed
Inspector’s note: NO HOT WATER PROVIDED AT GIRL'S AND BOY'S WASHROOMS, ROOM #100 AND ROOM #101. ALSO GIRL'S WASHROOM HAD NO WATER FLOW.PRESENT WATER TEMPERATURE FROM 50F TO 54.5F. INSTRUCTED TO PROVIDE HOT WATER AND any self-closing, slow closing, or metering faucet used shall be designed to provide a flow of water for at least 15 seconds without the need to reactivate the faucet. Steam-mixing valves are prohibited. INSTRUCTED ENGINEER FOR THE CHILDREN TO USE WASHBOWL IN STAFF WASHROOM(ROOM #112), HOT AND COLD RUNNING WATER IS PROVIDED. SERIOUS VIOLATION: 7-38-030.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Re seal baseboard/coving on wall by the kitchen staff washroom
-
-
Pass
Canvass · Pass
1 general Show violations
-
GeneralMinor (pre-2018 form)
Lighting: required minimum foot-candles of light provided, fixtures shielded
Inspector’s note: Replace broken light shield in room 106 and 107. Breakfast and lunch is consumed in each class room.
-
-
Pass
Canvass · Pass
4 general Show violations
-
GeneralMinor (pre-2018 form)
Food and non-food contact surfaces properly designed, constructed and maintained
Inspector’s note: Rusted lid of the grease trap box under the 3 compartment sink. Must remove rust and maintain.
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: Floor behind the reach in cooler with milk, needs detail cleaning and maintain.
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Peelng paint on the walls behind the washbowl sink in room 101/ library. Must remove /scrape peeling paint and maintain.
-
GeneralMinor (pre-2018 form)
Only authorized personnel in the food-prep area
Inspector’s note: Only authorized personnel in the food prep area. Observed male employee passing from the exit door towards the prep area and exit on the front entrance door of the prep area/kitchen not wearing hair restraint,while food service employees are preparing thr foods for lunch.
-
-
Pass
Canvass · Pass
1 general Show violations
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: Damaged ceiling tiles in room 100. Must replace and maintain.
-
-
Pass
Canvass · Pass
5 general Show violations
-
GeneralMinor (pre-2018 form)
Floors: constructed per code, cleaned, good repair, coving installed, dust-less cleaning methods used
Inspector’s note: floors in storage areas, bathrooms, and boiler rooms not clean need cleaning(corners).
-
GeneralMinor (pre-2018 form)
Walls, ceilings, attached equipment constructed per code: good repair, surfaces clean and dust-less cleaning methods
Inspector’s note: peeling paint, exposed plaster in kitchen prep area shall be repair. damaged, stained ceiling tiles in gym, classrooms shall be repair/replaced.
-
GeneralMinor (pre-2018 form)
Lighting: required minimum foot-candles of light provided, fixtures shielded
Inspector’s note: light shields in kitchen prep area, need cleaning. missing, broken light shields in bathrooms, classrooms shall be replaced.light shields in classrooms, hallways need cleaning.
-
GeneralMinor (pre-2018 form)
Toilet room doors self closing: dressing rooms with lockers provided: complete separation from living/sleeping quarters
Inspector’s note: missing self closing mechanism to bathroom door in room #101, boiler room bathroom shall be provided.
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: exhaust vents(ventilation) in classrooms, bathrooms, and hallways not clean need cleaning.
-
-
Pass
Canvass · Pass
1 general Show violations
-
GeneralMinor (pre-2018 form)
Ventilation: rooms and equipment vented as required: plumbing: installed and maintained
Inspector’s note: The flow of air discharged from kitchen fans shall always be through a duct to a point above the roofline. REPAIR LEAK FROM PIPE IN BOILER ROOM PIT, MAINTAIN DRY FLOOR. REPAIR VENTILATION IN KITCHEN EMPLOYEE WASHROOM. INCREASE FLOW TIME IN BOYS WASHROOM ACROSS FROM ROOM 105, 1ST FLOOR.
-
More in ZIP 60645